2015-07-27 15:26:551ST REVIEW: FBC 2014 5TH ED.
  
 THE WIND LOAD CALCULATIONS SUPPLIED DO NOT CONTAIN
 INFORMATION TO ALLOW FOR DETERMINATION THAT SUCH
 CALCULATIONS APPLY TO THIS PROJECT. THERE IS NO JOB
 IDENTIFICATION OR ADDRESS FOR THE JOB UPON THE THE
 SUBMITTAL BY JERROD K. FRANKLIN, PE 60641. THERE IS NO
 WAY TO DETERMINE THAT THE INSTALLATION ON SHEET E-4 IS
 CONSISTENT WITH THE CALCULATIONS OR THAT THE
 CALCULATIONS ARE BASED UPON THE DETAIL SHOWN THERE.
 ADDITIONALLY, NOTE 4 REQUIRES A SHOP DRAWING SUBMITTAL
 WITH WIND LOAD CALCULATIONS AND EMBEDMENT DETAILS. SUCH
 SHOP SUBMITTAL MUST ADDITIONALLY BE REVIEWED BY LARRY
 M. SMITH, PE 45997 FOR CONSISTENCY WITH HIS
 SPECIFICATIONS.
  