| Notes |
| Date |
Text |
| 2015-07-27 15:26:55 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | THE WIND LOAD CALCULATIONS SUPPLIED DO NOT CONTAIN | | | INFORMATION TO ALLOW FOR DETERMINATION THAT SUCH | | | CALCULATIONS APPLY TO THIS PROJECT. THERE IS NO JOB | | | IDENTIFICATION OR ADDRESS FOR THE JOB UPON THE THE | | | SUBMITTAL BY JERROD K. FRANKLIN, PE 60641. THERE IS NO | | | WAY TO DETERMINE THAT THE INSTALLATION ON SHEET E-4 IS | | | CONSISTENT WITH THE CALCULATIONS OR THAT THE | | | CALCULATIONS ARE BASED UPON THE DETAIL SHOWN THERE. | | | ADDITIONALLY, NOTE 4 REQUIRES A SHOP DRAWING SUBMITTAL | | | WITH WIND LOAD CALCULATIONS AND EMBEDMENT DETAILS. SUCH | | | SHOP SUBMITTAL MUST ADDITIONALLY BE REVIEWED BY LARRY | | | M. SMITH, PE 45997 FOR CONSISTENCY WITH HIS | | | SPECIFICATIONS. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|