| 2015-08-01 10:15:05 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. SEE CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE SECTION 107: |
| | |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS |
| | 107.2.1 THROUGH 107.2.5. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| | CODE AND RELEVANT LAWS, ORDINANCES, RULES |
| | AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE |
| | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| | CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | STRUCTURAL DETAILS FOR WALL AND ROOF FRAMING ARE NOT |
| | PROVIDED. AS THIS AFFECTS EXTERIOR WALLS (BUILDING |
| | ENVELOPE) EITHER PROVIDE ENGINEERING FOR STRUCTURAL |
| | LOAD BEARING ELEMENTS OR REVISE PLAN TO STATE DESIGN |
| | CRITERIA (FBC 5TH EDITION RESIDENTIAL 301.1). IF ASCE7 |
| | IS USED AS DESIGN CRITERIA AND PLANS ARE NOT PREPARED |
| | BY A DESIGN PROFESSIONAL, PROVIDE CALCULATIONS FOR |
| | STRUCTURAL ELEMENTS (FRAMING, CONNECTORS). |
| | |
| | 2. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 5TH |
| | EDITION RESIDENTIAL 301.2.1. |
| | |
| | 3. REVISE PLAN TO INCLUDE METHOD OF COMPLIANCE |
| | SELECTED, FBC 5TH EDITION EXISTING BUILDING CODE 301.1. |
| | |
| | 4. VALUE IS UNREASONABLY LOW. PROVIDE AN ACCURATE |
| | VALUE. VALUE IS TO INCLUDE THE MARKET VALUE OF LABOR, |
| | MATERIALS, OVERHEAD, PROFIT, ENGINEERING - EVERYTHING |
| | EXCEPT FOR LAND, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE SECTION 109. WHEN PROVIDING |
| | THE VALUE, PROVIDE A COST BREAKDOWN ITEM BY ITEM. IF IT |
| | IS DETERMINED THAT THE VALUE IS STILL UNREASONABLY LOW, |
| | VALUE WILL BE BALLPARKED. IF APPLICANT OBJECTS, A STICK |
| | ESTIMATE WILL BE DONE BUT BE AWARE THAT THIS WILL DELAY |
| | PLAN REVIEW DUE TO THE LENGTH OF TIME REQUIRED. |
| | |
| | 5. A STOP WORK VIOLATION HAS BEEN ISSUED. PLANS |
| | PROVIDED DO NOT MEET THE MINIMUM REQUIREMENTS FOR PLANS |
| | (SEE COMMENT 1). IF A DESIGN PROFESSIONAL IS HIRED, |
| | SEND A COPY OF THE CONTRACT. APPLICANT WAS GIVEN 30 |
| | DAYS TO OBTAIN A PERMIT. EXTENSIONS WILL NOT BE GRANTED |
| | WITHOUT EVIDENCE THAT CONTRACTOR IS PURSUING RESOLUTION |
| | (EITHER A COMPETENT DESIGN PROFESSIONAL HIRED, OR PLANS |
| | RESUBMITTED). |
| | |
| | 6. PLANS SHOW "EXISTING SMOKE DETECTORS." I WAS UNABLE |
| | TO LOCATE AN ELECTRICAL PERMIT FOR THIS ADDRESS FOR |
| | THIS ITEM. PROVIDE MORE INFORMATION, FBC 107. IF |
| | ADDITIONAL WORK WAS DONE WITHOUT PERMITS ON THIS |
| | STRUCTURE WHICH WAS NOT INCLUDED ON THE STOP WORK |
| | VIOLATION, REVISE PLAN TO INCLUDE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |