| 2015-09-25 08:57:35 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15070192 | | | 9/25/15 | | | | | | 1) REFER TO COMMENT #1 FROM THE 1ST REVIEW. AS NOTED IN | | | THE COMMENT, SEPARATE PERMITS ARE REQUIRED FOR KITCHEN | | | HOODS AND FIRE SUPPRESSION SYSTEMS. FOR CLARIFICATION | | | PURPOSES, PLEASE PLACE A NOTE ON THE MECHANICAL PLANS | | | TO THAT EFFECT AND INDICATE THE HOOD DRAWINGS AND | | | DETAILS ARE FOR REFERENCE ONLY. | | | 2) REFER TO COMMENT #3 FROM THE 1ST REVIEW: THE PLANS | | | ARE NOT IN COMPLIANCE WITH SECTION 508.1 FBC-14 | | | MECHANICAL. SEE SHEET M-3.1, KITCHEN PRESSURIZATION: | | | THE AMOUNT OF MAKE UP AIR CFM'S FOR THE EXHAUST SYSTEMS | | | SHOWN IN THE SCHEDULE IS NOT APPROXIMATELY EQUAL TO THE | | | AMOUNT OF EXHAUST AIR CFM'S AS REQUIRED BY CODE. IN | | | ADDITION THE SCHEDULES DO NOT CLEARLY INDICATE HOW MUCH | | | OF THE O/A FORM AC-1 IS PROVIDED FOR OCCUPANTS (AS | | | REQUIRED BY THE O/A SCHEDULE) OR HOW MUCH IS PROVIDED | | | FOR COOKING APPLIANCE COMBUSTION. PLEASE CLARIFY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|