2015-09-25 08:57:352ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070192
 9/25/15
  
 1) REFER TO COMMENT #1 FROM THE 1ST REVIEW. AS NOTED IN
 THE COMMENT, SEPARATE PERMITS ARE REQUIRED FOR KITCHEN
 HOODS AND FIRE SUPPRESSION SYSTEMS. FOR CLARIFICATION
 PURPOSES, PLEASE PLACE A NOTE ON THE MECHANICAL PLANS
 TO THAT EFFECT AND INDICATE THE HOOD DRAWINGS AND
 DETAILS ARE FOR REFERENCE ONLY.
 2) REFER TO COMMENT #3 FROM THE 1ST REVIEW: THE PLANS
 ARE NOT IN COMPLIANCE WITH SECTION 508.1 FBC-14
 MECHANICAL. SEE SHEET M-3.1, KITCHEN PRESSURIZATION:
 THE AMOUNT OF MAKE UP AIR CFM'S FOR THE EXHAUST SYSTEMS
 SHOWN IN THE SCHEDULE IS NOT APPROXIMATELY EQUAL TO THE
 AMOUNT OF EXHAUST AIR CFM'S AS REQUIRED BY CODE. IN
 ADDITION THE SCHEDULES DO NOT CLEARLY INDICATE HOW MUCH
 OF THE O/A FORM AC-1 IS PROVIDED FOR OCCUPANTS (AS
 REQUIRED BY THE O/A SCHEDULE) OR HOW MUCH IS PROVIDED
 FOR COOKING APPLIANCE COMBUSTION. PLEASE CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER