2015-08-13 08:50:121ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070192
 8/13/15
  
 1) THE CITY OF WEST PALM BEACH CONSTRUCTION SERVICES
 DIVISION REQUIRES SEPARATE PERMITS FOR KITCHEN HOODS
 AND FIRE SUPPRESSION. PLEASE PLACE A NOTE ON THE PLAN
 ACCORDINGLY TO CLARIFY AND LABEL ALL HOOD DETAILS AS
 "FOR REREFENCE ONLY"
 2) NO VALUE IS INDICATED FOR THE PROPOSED PROJECT ON
 THE PERMIT APPLICATION. REFER TO SECTION 109.3 WPB
 AMENDMENTS TO THE FLORIDA BUILDING CODE 2010 BUILDING
 PERMIT VALUATIONS:
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED, UNLESS THE APPLICANT
 CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE
 SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND
 PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES
 MAY INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL
 CODE CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE
 SET BY THE BUILDING OFFICIAL.
 *PLEASE NOTE THAT THE VALUES FOR THE HOOD AND FIRE
 SUPPRESSION PROJECT MUST BE BROKEN OUT FROM THE TOTAL
 VALUE OF THIS PERMIT APPLICATION.
 3) PLEASE REVIEW THE FOLLOWING COMMENTS IN REREFENCE TO
 THE FUTURE HOOD AND FIRE SUPPRESSION PERMIT APPLICATION
 AND PLANS.
 A) REFERENCE SECTION 508.1 FBC-14 MECHANICAL AND SHOW
 COMPLIANCE:
 MAKEUP AIR.
 MAKEUP AIR SHALL BE SUPPLIED DURING THE OPERATION OF
 COMMERCIAL KITCHEN EXHAUST SYSTEMS THAT ARE PROVIDED
 FOR COMMERCIAL COOKING APPLIANCES. THE AMOUNT OF MAKEUP
 AIR SUPPLIED TO THE BUILDING FROM ALL SOURCES SHALL BE
 APPROXIMATELY EQUAL TO THE AMOUNT OF EXHAUST AIR FOR
 ALL EXHAUST SYSTEMS FOR THE BUILDING. THE MAKEUP AIR
 SHALL NOT REDUCE THE EFFECTIVENESS OF THE EXHAUST
 SYSTEM.MAKEUP AIR SHALL BE PROVIDED BY GRAVITY OR
 MECHANICAL MEANS OR BOTH. MECHANICAL MAKEUP AIR SYSTEMS
 SHALL BE AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM. MAKEUP AIR
 INTAKE OPENING LOCATIONS SHALL COMPLY WITH SECTION
 401.4.
 *PLEASE CLARIFY HOW THE PROPOSED SYSTEM IS MEETING
 COMPLIANCE WITH THIS SECTION- 1) HOW MUCH OF THE AIR
 LISTED IN THE SCHEDULE ON SHEET M-3.1 IS FOR THE HOOD
 MAKEUP AIR, AND HOW MUCH FOR CONDITIONING THE SPACE?
 PLEASE NOTE THAT SHEET M-1.1 INDICATES THE CLOSEST
 DIFFUSER TO THE HOOD IS SUPPLYING 630 CFM. 2) HOW IS
 THE MAKEUP LINKED TO OPERATE AUTOMATICALLY WITH THE
 EXHAUST SYSTEM?
 B) REFERENCE SECTION 506.3.4 AND PROVIDE AN AIR
 VELOCITY CALCULATION FOR THE PROPOSED GREASE EXHAUST
 DUCT.
 C) REFERENCE SECTION 507.9 AND SHOW COMPLIANCE:
 CLEARANCES FOR TYPE I HOOD.
 A TYPE I HOOD SHALL BE INSTALLED WITH A CLEARANCE TO
 COMBUSTIBLES OF NOT LESS THAN 18 INCHES (457 MM).
 EXCEPTION: CLEARANCE SHALL NOT BE REQUIRED FROM GYPSUM
 WALLBOARD OR 1/2-INCH (12.7 MM) OR THICKER CEMENTITIOUS
 WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES
 PROVIDED THAT A SMOOTH, CLEANABLE, NONABSORBENT AND
 NONCOMBUSTIBLE MATERIAL IS INSTALLED BETWEEN THE HOOD
 AND THE GYPSUM OR CEMENTITIOUS WALLBOARD OVER AN AREA
 EXTENDING NOT LESS THAN 18 INCHES (457 MM) IN ALL
 DIRECTIONS FROM THE HOOD.
 C) SHEET M-4.1: SUBMIT TWO COPIES OF A CURRENT FLORIDA
 PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE ROOF MOUNTED
 EXHAUST FAN AND CURB. REFER TO FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWING.
 D) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE FYREWRAP REVIEWED
 ANSD APPROVED BY THE DESIGN PROFESSIONAL OF RECORD.
  