Plan Review Notes
Plan Review Notes For Permit 15070192
Permit Number 15070192
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-12 15:36:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070192
 ADD: 2070 PALM BEACH LAKES / CHICK-FIL-E
 CONT: TBD (TO BE DETERMINED)
 TEL: (?????????????????? NOT PROVIDED ON APPLICATION
 E-MAIL:???????????????? NOT PROVIDED ON APPLICATION
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 12/ 2015
 ACTION: DENIED
  
 1) SHEET A-1.7 ROOF TOP PLAN HAS A NOTE ABOUT AVCOA
 ALUMINUM EQUIPMENT STAND. THE NOTE STATES THE FREEZER/
 COOLER AND ICE MAKER CONDENSORS ARE TO REMAIN. IS THE
 EQUIPMENT STAND ITSELF BEING REPLACED? IF SO THEN
 PROVIDE A PRODUCT APPROVAL FOR THE STAND, IF
 PRE-ENGINEEERED. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(G) PRE-ENGINEERED A/C STAND.
 SEE 2014 FBC-B TABLE 1509.6.5.
  
 2) PLEASE BE AWARE IF THERE IS WORK BEING COMPLETED ON
 EITHER THE A/C CONDENSOR STAND OR THE EQUIPMENT ITSELF
 THAT IS WITHIN 10 FT. OF THE PARAPET WALL, IF THE
 PARAPET WALL IS NOT 42 INCHES TALL THEN COMPLIANCE WITH
 2014 FBC-B 1013.6 WOULD BE REQUIRED.
  
 3) SHEET A-1.7 ALSO SHOWS A NEW ROOF TOP EXHAUST FAN
 AND CURB. PLEASE PROVIDE PRODUCT APPROVALS FOR BOTH THE
 ROOF TOP CURB AND EXHAUST FAN.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES & FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) PLEASE PROVIDE STRUCTURAL DETAILS OF THE NEW HOLE TO
 BE CUT INTO THE ROOF DECK. PROVIDE REINFORING OF THE
 NEW HOLE, IF BAR JOIST OR WOOD TRUSSES, BRACING FOR THE
 POINT LOAD, AS WELL AS THE ANCHORING OF THE EXHAUST FAN
 CURB TO THE ROOF DECK AND THE CURB TO THE BODY OF THE
 EXHAUST FAN. CURB TO TO BE ATTACHED TO FRAMING MEMBERS,
 PART OF THE MWFRS. MAIN WIND FORCE RESISTING SYSTEM.
 1609.6.4.4.1.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  