| 2016-05-19 17:07:07 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) FLAT ROOF OVER NEW ENTRY. AND, CLEARLY MARK SELECTED |
| | APPROVED ASSEMBLY. IF SELECTED ASSEMBLY DOESN'T MEET |
| | THE CALCULATED DESIGN PRESSURES, THEN NEED TO SUBMIT |
| | SIGNED AND SEALED RAS 117 CALCULATIONS (IF THE SELECTED |
| | ASSEMBLY ALLOWS IT). |
| | RESPONSE: NO INFORMATION WAS SUBMITTED. |
| | |
| | B) SOLATUBE SKYLIGHTS AS SHOWN ON PLANS. |
| | RESPONSE: FLORIDA PRODUCT APPROVAL FL11480-R4 SUBMITTED |
| | IS FOR 2010 FBC AND WAS VALIDATED NOT APPROVED. IN |
| | ADDITION THE MIAMI-DADE NOA 03-1016.01 SUBMITTED |
| | EXPIRED IN NOVEMBER 13, 2009. NEED TO PROVIDE |
| | CURRENT/APPROVED PRODUCT APPROVAL. |
| | |
| | 2- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | RESPONSE: RESPONSE LETTER SAID:: "SEE ATTACHED LETTER". |
| | THERE WAS NO ATTACHED LETTER IN THE RESUBMITTED |
| | PACKAGE. NOTE: IF ENGINEER IS PROVIDING A LETTER |
| | INSTEAD OF PROVIDING REVIEW STAMP ON EACH PRODUCT |
| | APPROVAL, THEN CLEARLY IDENTIFY EACH PRODUCT FLORIDA |
| | PRODUCT APPROVAL NUMBER, NOA NUMBER AND SPECIFIC MODEL |
| | FOR EACH PRODUCT APPROVAL REVIEWED. |
| | |
| | |
| | APPROVED PRODUCT APPROVALS: |
| | 1- ROOF TILE ADHESIVE FL6332-R5. |
| | |
| | 2- ROOF TILE FL7804-R8 |