Plan Review Notes
Plan Review Notes For Permit 15070174
Permit Number 15070174
Review Stop B
Sequence Number 2
Notes
Date Text
2016-05-16 09:21:04RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION(2014).
  
 NEW COMMENT:
 1- NEED TWO SETS OF PLANS WITH ENGINEER'S ORIGINAL SEAL
 AND SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. ONE OF
 THE SETS SUBMITTED IS A COPY. NEED BOTH SETS WITH
 ORIGINAL SEAL AND SIGNATURE.
  
 NEW COMMENT:
 2- ENGINEER OF RECORD IS USING A SEAL THAT READS
 "CERTIFICATE". THIS TYPE OF SEAL IS NOT LONGER VALID
 SINCE JANUARY 2006. ENGINEER NEEDS TO USE CURRENT SEAL
 THAT READS "LICENSE" AS REQUIRED BY 61G15-23.002 F.A.C.
  
 3- SHEET A-1:
 A) NEW BOLD LETTERING AND NUMBERING SHOWN ON ALL PLANS
 IS NOT LEGIBLE. LETTERS AND NUMBERS ARE TOO CLOSE
 TOGETHER. THEY ARE TOO DIFFICULT TO READ. DRAWINGS ARE
 NOT CLEAR FOR RECORD RETENTION PURPOSES. REVISE AS
 REQUIRED PROVIDE LEGIBLE INFORMATION. SEC. 107.2.1.4
 CITY AMENDMENTS.
  
 COMMENT:
 B) PROVIDE COMPLETE SPECIFICATIONS FOR THE GARAGE DOOR
 LEADING TO THE SECOND FLOOR STAIRWAY SHOWING COMPLIANCE
 WITH SEC. R302.5.1 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). NOTE THAT SELF CLOSING DOORS ARE REQUIRED ALSO.
 RESPONSE: DOOR SCHEDULE ON SHEET A-3 STILL DOESN'T
 PROVIDE SPECIFICATIONS FOR DOOR #7 SHOWING COMPLIANCE
 WITH SEC. R302.5.1.
  
 COMMENT:
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW WINDOW OPENING NEXT TO THE NEW ENTRY DOORS. SPECIFY
 OPENING SIZE AND PROVIDE COMPLETE FRAMING
 DETAILS/SPECIFICATIONS. SEC. R301.
 RESPONSE: THERE ARE NO FRAMING SPECIFICATIONS PROVIDED.
  
 COMMENT:
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW STAIRWAY. PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
 RESPONSE: NO FRAMING DETAILS PROVIDED.
  
 COMMENT:
 E) MASTER BEDROOM WINDOWS DON'T COMPLY WITH THE EGRESS
 REQUIREMENTS OF SEC. R310. (ALSO, CLEARLY SPECIFY EACH
 WINDOW TYPE ON THE WINDOW SCHEDULE. SINGLE HUNG, ETC.).
 RESPONSE: UNABLE TO VERIFY. INFORMATION ON THE WINDOW
 SCHEDULE IS NOT LEGIBLE. BOLD LETTERING IS NOT LEGIBLE.
 ALSO, SEE SINGLE HUNG PRODUCT APPROVAL SUBMITTED FOR
 SIZE OF WINDOW SPECIFIED. IT LOOKS LIKE A 24 SINGLE
 HUNG WINDOW DOESN'T COMPLY. PROVIDE MANUFACTURER'S CUT
 SHEET SHOWING THAT THE SPECIFIED WINDOW MEETS THE TOTAL
 CLEAR HEIGHT OF 24" AND TOTAL CLEAR OPENING OF 5.7 S.F.
  
 COMMENT:
 F) SPECIFY ATTIC ACCESS. SIZE AND LOCATION TO COMPLY
 WITH SEC. R807.
 RESPONSE: INFORMATION SHOWN ON SECOND FLOOR PLAN IS NOT
 LEGIBLE. UNABLE TO VERIFY SIZE.
  
 COMMENT:
 4- SPECIFY CARBON MONOXIDE ALARM BY ALL BEDROOMS (
 PROPOSED AND EXISTING) AS REQUIRED BY SEC. R315.
 RESPONSE: NEED TO PROVIDE SPECIFICATIONS FOR THE
 INSTALLATION OF CARBON MONOXIDE ALARMS WITH 10 FETT OF
 ALL EXISTING BEDROOMS.
  
 COMMENT:
 5- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 OF FBC-EXISTING BUILDING, 5TH EDITION (2014).
 NOTE: COORDINATE PLANS AND ENERGY CALCULATIONS TO AVOID
 CONFLICTS AND UNNECESSARY DELAYS.
 RESPONSE: A) PROVIDE COMPLETE AND CORRECT INFORMATION
 ON TOP OF FORM R405-2014 SUBMITTED. PROVIDE BUILDER'S
 NAME AND THE JURISDICTION NUMBER IS INCORRECT. REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 B) PROVIDE ALL INFORMATION REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014) INCLUDING:
 (1)INSPECTION CHECKLIST, (2) NAME OF PERSON PREPARING
 THE ENERGY CALCULATIONS,
  
 C) OWNER/AGENT TO CERTIFY BOTTOM OF FORM AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 D) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD SUBMITTED. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 COMMENT:
 6-SHEET A-2: WINDOWS AND DOORS DESIGN PRESSURES DON'T
 CORRESPOND TO EXPOSURE"C". REVISE ALL THE DESIGN
 PRESSURES AS REQUIRED. SEC. R301.
 RESPONSE: DESIGN PRESSURES SHOWN ON EXTERIOR ELEVATIONS
 ARE NOT LEGIBLE.
  
 COMMENT:
 7- SHEET A-3:
 A) SPECIFY THE INTERNAL PRESSURES COEFFICIENT. AND,
 CLARIFY WHAT'S ASCI 7.05? DO YOU MEAN ASCE? . ( NOTE:
 FBC 2014 REFERENCES THE ASCE 7-10 NOT ASCE-05). SEC.
 107.2.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT.. NOT ADDRESSED.
  
 B) CLEARLY SPECIFY ALL DEAD AND LIVE LOADS, INCLUDING
 THE ATTIC LIVE LIVE LOAD AS REQUIRED BY NOTES "B" AND
 "G" OF TABLE R301.5. NOTE: CLEARLY SPECIFY THE LOADS
 FOR SECOND FLOOR, ROOF, ETC.
 RESPONSE: COORDINATE INFORMATION GIVEN HERE WITH
 INFORMATION GIVEN ON SHEET RE-NAMED "SITE". SEE ITEM #
 8(2) BELOW.
  
 C) SPECIFY ON THE TYPICAL WALL SECTION THE MIN. FOOTING
 DEPTH AS REQUIRED BY SEC. R404.16. NOTE: SIZE OF
 FOUNDATION ON SHEET A-1 MAY NEED TO BE REVISED.
 COORDINATE WITH FINISH GRADE ITEM ABOVE.
 RESPONSE: REPEAT COMMENT.NOT ADDRESSED. NOTE: "TYPICAL
 FOOTER CONSTRUCTION" SPECIFIES 14" X 24" CONCRETE
 MONOLITHIC FOOTER. THIS SIZE OF FOOTING DOESN'T MATCH
 SIZE SPECIFIED ON THE FOUNDATION PLAN AND IT DOESN'T
 PROVIDE THE REQUIRED 12" MIN. FOOTING DEPTH. REVISE AS
 REQUIRED.
  
 D) ENGINEER OF RECORD TO SPECIFY THE ROOF TILE
 FASTENING SPECIFICATIONS AS REQUIRED BY SEC. 107.2.1.2
 CITY AMENDMENTS. IF USING NAILS, THEN SPECIFY TYPE,
 SIZE AND NUMBER OF NAILS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 E) REVISE ROOF SHEATHING FASTENING SPECIFICATIONS ON
 TYPICAL WALL SECTION. SEC. R803.2.3.1 REQUIRES RING
 SHANK NAILS.
 RESPONSE: THERE ARE TWO OPTIONS SPECIFIED. RING SHANK
 NAILS ARE REQUIRED. OTHERWISE, ENGINEER TO PROVIDE
 CALCULATIONS SHOWING THAT THE 8D COMMON NAILS SPECIFIED
 ON THE SECOND OPTION PROVIDE THE SAME RESISTANCE AS THE
 8D RING SHANK NAILS.
 NOTE: COORDINATE INFORMATION WITH NOTE #45 ON SHEET
 RE-NAMED "SITE".
  
 F) "TYPICAL EXTERIOR WALL CONSTRUCTION" NOTE SHOWN ON
 TYP. WALL SECTION DOESN'T MATCH LOCATION AND TYPE OF
 COLUMNS SHOWN ON FOUNDATION PLAN. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 COMMENT:
 8- SHEET S-1: (1) NEED TO PROVIDE ENGINEER OF RECORD
 INFORMATION AND DRAWING NEEDS TO BE SIGNED AND SEALED.
 THIS SHEET CONTAINS STRUCTURAL SPECIFICATIONS. CHAPTER
 471 F. S. THIS SHEET CONTAINS STRUCTURAL
 SPECIFICATIONS. (2) UPDATE ALL NOTES REFERENCING THE
 CURRENT 2014 FBC.
 RESPONSE: SHEET WAS RENAMED AS SITE:
 (1) REVISE NOTE #2. THERE IS NOT ASCE 2014.
  
 (2) REVISE LOADS SPECIFIED ON NOTE #6. ROOF DEAD LOAD
 APPEARS TO BE TOO LOW FOR THE TYPE OF ROOFING MATERIAL
 TO BE USED. ALSO, CLARIFY WHY ARE THERE TWO DIFFERENT
 ATTIC LIVE LOADS..
  
 COMMENT:
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOORS AS SHOWN ON PLANS.
 RESPONSE: MIAMI-DADE NOA 14-0204.08 DOESN'T MEET THE
 DESIGN PRESSURES CALCULATED BY THE ENGINEER OF RECORD.
  
 B) FLAT ROOF OVER NEW ENTRY. AND, CLEARLY MARK SELECTED
 APPROVED ASSEMBLY. IF SELECTED ASSEMBLY DOESN'T MEET
 THE CALCULATED DESIGN PRESSURES, THEN NEED TO SUBMIT
 SIGNED AND SEALED RAS 117 CALCULATIONS (IF THE SELECTED
 ASSEMBLY ALLOWS IT).
 RESPONSE: NO INFORMATION WAS SUBMITTED.
  
 C) SOLATUBE SKYLIGHTS AS SHOWN ON PLANS.
 RESPONSE: FLORIDA PRODUCT APPROVAL FL11480-R4 SUBMITTED
 IS FOR 2010 FBC AND WAS VALIDATED NOT APPROVED. IN
 ADDITION THE MIAMI-DADE NOA 03-1016.01 SUBMITTED
 EXPIRED IN NOVEMBER 13, 2009. NEED TO PROVIDE
 CURRENT/APPROVED PRODUCT APPROVAL.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. AND CLEARLY
 SPECIFY/MARK MULLION SIZE TO VERIFY THE DESIGN
 PRESSURES.
 RESPONSE: NO INFORMATION WAS SUBMITTED.
  
 10- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE: RESPONSE LETTER SAID:: "SEE ATTACHED LETTER".
 THERE WAS NO ATTACHED LETTER IN THE RESUBMITTED
 PACKAGE. NOTE: IF ENGINEER IS PROVIDING A LETTER
 INSTEAD OF PROVIDING REVIEW STAMP ON EACH PRODUCT
 APPROVAL, THEN CLEARLY IDENTIFY EACH PRODUCT FLORIDA
 PRODUCT APPROVAL NUMBER, NOA NUMBER AND SPECIFIC MODEL
 FOR EACH PRODUCT APPROVAL REVIEWED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. SUBMIT
 OLD COPIES FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]