2015-09-10 19:47:42RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE: COORDINATE EQUIPMENT SIZING CALCULATIONS WITH THE
 ENERGY CALCULATIONS AND THE PLANS SUBMITTED TO AVOID
 CONFLICTS OR DELAYS.
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS:
 A) THE INTERIOR DESIGN CONDITIONS NEED TO COMPLY WITH
 SEC. R302.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) CALCULATIONS NEED TO MATCH PLANS. REVISE THE
 BUILDING ORIENTATION, WALLS INFORMATION (PLANS DON'T
 SHOW R10 INSULATION), WINDOWS INFORMATION, CEILINGS
 INFORMATION (PLANS DON'T SHOW R-20 ROOF INSULATION AND
 R-30 CEILING INSULATION), FLOOR INFORMATION, CEILING
 HEIGHT INFORMATION, NUMBER OF OCCUPANTS, ETC. SEC.
 R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 2- PROVIDE COMPLETE MANUFACTURER'S INFORMATION FOR THE
 SELECTED EQUIPMENT INCLUDING THE ARI REF. NO. SEC.
 R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 3- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE A/C PLAN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS.
  
 ***PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
  