| 2015-09-14 17:33:05 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. INDICATE THE SCALE TO WHICH THE DRAWINGS WERE MADE. |
| | 2. PER FBC-R 315, YOU SHALL HAVE A CARBON MONOXIDE |
| | ALARM WITHIN 10' OF EACH BEDROOM. |
| | 3. PER FBC-R 314.3.1, YOU SHALL UPGRADE YOUR SMOKE |
| | DETECTOR COVERAGE FOR THE ENTIRE RESIDENCE TO MEET THE |
| | SAME REQUIREMENTS AS A NEW HOME. |
| | 4. OUTLETS SHALL BE SPACED AS INSTRUCTED IN NEC |
| | 210.52(A). |
| | 5. PER NEC 220.16, YOU SHALL PROVIDE AN ELECTRICAL |
| | RISER DIAGRAM AND LOAD CALCULATION FOR THE EXISTING |
| | HOME AS WELL AS THE ADDITION TO ASCERTAIN AVAILABILITY |
| | OF SURPLUS TO ACCEPT THE ADDED LOAD. |
| | 6. ON THE SITE PLAN, SHEET S1, INDICATE THE LOCATION OF |
| | THE EXISTING SERVICE, INCLUDING BOTH METER AND |
| | DISCONNECT. MARK THE LOCATION OF THE SERVICE POLE AND |
| | THE LOCATION OF PANEL ?A?, (PRIMARY PANEL). |
| | 7. INDICATE ON THE FLOOR PLAN THE LOCATION OF THE HVAC |
| | AND ALL FIXED APPLIANCES INDICATED ON PANEL B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |