2015-09-14 17:33:05PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. INDICATE THE SCALE TO WHICH THE DRAWINGS WERE MADE.
 2. PER FBC-R 315, YOU SHALL HAVE A CARBON MONOXIDE
 ALARM WITHIN 10' OF EACH BEDROOM.
 3. PER FBC-R 314.3.1, YOU SHALL UPGRADE YOUR SMOKE
 DETECTOR COVERAGE FOR THE ENTIRE RESIDENCE TO MEET THE
 SAME REQUIREMENTS AS A NEW HOME.
 4. OUTLETS SHALL BE SPACED AS INSTRUCTED IN NEC
 210.52(A).
 5. PER NEC 220.16, YOU SHALL PROVIDE AN ELECTRICAL
 RISER DIAGRAM AND LOAD CALCULATION FOR THE EXISTING
 HOME AS WELL AS THE ADDITION TO ASCERTAIN AVAILABILITY
 OF SURPLUS TO ACCEPT THE ADDED LOAD.
 6. ON THE SITE PLAN, SHEET S1, INDICATE THE LOCATION OF
 THE EXISTING SERVICE, INCLUDING BOTH METER AND
 DISCONNECT. MARK THE LOCATION OF THE SERVICE POLE AND
 THE LOCATION OF PANEL ?A?, (PRIMARY PANEL).
 7. INDICATE ON THE FLOOR PLAN THE LOCATION OF THE HVAC
 AND ALL FIXED APPLIANCES INDICATED ON PANEL B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  