| 2015-09-02 14:29:33 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC-5TH EDITION(2014). |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- AS OF JUNE 30TH, 2015 THE NEW CODE IN EFFECT IS THE |
| | FBC-5TH EDITION(2014). PERMIT APPLICATION WAS SUBMITTED |
| | ON JULY 6TH 2015. THEREFORE, ALL THE PLANS AND NOTES |
| | NEED TO BE UPDATED TO THE CURRENT CODE FBC -5TH EDITION |
| | (2014). |
| | |
| | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT (EVEN FOR OWNER |
| | BUILDER) AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED |
| | BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS UPDATED TO |
| | $115,113. THE PERMIT FEE BALANCE IS $2671.80. |
| | |
| | 4- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 5- SHEET A-1: |
| | A) IDENTIFY ALL ROOMS THAT ARE ADJACENT TO THE NEW |
| | GARAGE ADDITION ( NEED TO VERIFY EGRESS FROM ANY |
| | BEDROOMS AND MECHANICAL VENTILATION FOR BATHROOMS. SEC. |
| | 701.2 OF FBC-EXISTING BUILDING, 5TH EDITION (2014). |
| | |
| | B) PROVIDE COMPLETE SPECIFICATIONS FOR THE GARAGE DOOR |
| | LEADING TO THE SECOND FLOOR STAIRWAY SHOWING COMPLIANCE |
| | WITH SEC. R302.5.1 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). NOTE THAT SELF CLOSING DOORS ARE REQUIRED ALSO. |
| | |
| | C) PROVIDE COMPLETE DETAILS AN SPECIFICATIONS FOR THE |
| | UNDER STAIR PROTECTION. R302.7 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | NEW WINDOW OPENING NEXT TO THE NEW ENTRY DOORS. SPECIFY |
| | OPENING SIZE AND PROVIDE COMPLETE FRAMING |
| | DETAILS/SPECIFICATIONS. SEC. R301. |
| | |
| | E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | NEW STAIRWAY AND HANDRAILS. PROVIDE COMPLETE FRAMING |
| | DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. |
| | R311.7 |
| | |
| | F) MASTER BEDROOM WINDOWS DON'T COMPLY WITH THE EGRESS |
| | REQUIREMENTS OF SEC. R310. (ALSO, CLEARLY SPECIFY EACH |
| | WINDOW TYPE ON THE WINDOW SCHEDULE. SINGLE HUNG, ETC.). |
| | |
| | G) SPECIFY ATTIC ACCESS. SIZE AND LOCATION TO COMPLY |
| | WITH SEC. R807. |
| | |
| | H) SECTION A/A-3 SHOWN ON SHEET A-3 DOESN'T MATCH |
| | SECTION LOCATION AS SHOWN ON SECOND FLOOR PLAN. AND, |
| | SEC. B/A-1 DOESN'T MATCH EITHER. SEC. 107.2.1 CITY |
| | AMENDMENTS. REVISE AS REQUIRED. |
| | |
| | I) REVISE WINDOW NOTES: BEVELED BUCKS ARE NOT ALLOWED |
| | AND REFERENCE CURRENT 2014 CODE. AND PROVIDE DOOR |
| | STRUCTURAL BUCK DETAIL AND SPECIFICATIONS. NOTE: BUCK |
| | SIZE TO PROVIDE FULL SUPPORT TO THE DOOR AND WINDOW |
| | FRAME. SEE SEC. R612.7.2. |
| | |
| | J) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | GARAGE STRUCTURAL BUCK. SEC. R301. |
| | |
| | 6- SPECIFY CARBON MONOXIDE ALARM BY ALL BEDROOMS |
| | (PROPOSED AND EXISTING) AS REQUIRED BY SEC. R315. |
| | |
| | 7- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106 |
| | OF FBC-EXISTING BUILDING, 5TH EDITION (2014). |
| | NOTE: COORDINATE PLANS AND ENERGY CALCULATIONS TO AVOID |
| | CONFLICTS AND UNNECESSARY DELAYS. |
| | |
| | 8- SHEET A-2: WINDOWS AND DOORS DESIGN PRESSURES DON'T |
| | CORRESPOND TO EXPOSURE"C". REVISE ALL THE DESIGN |
| | PRESSURES AS REQUIRED. SEC. R301. |
| | |
| | 9- SHEET A-3: |
| | A) REVISE WIND INFORMATION. THE CURRENT CODE IS THE |
| | FBC-5TH EDITION(2014). |
| | |
| | B) SPECIFY THE INTERNAL PRESSURES COEFFICIENT. CLARIFY |
| | WHAT'S ASCI 7.05? . ( NOTE: FBC 2014 REFERENCES THE |
| | ASCE 7-10). SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) CLEARLY SPECIFY ALL DEAD AND LIVE LOADS, INCLUDING |
| | THE ATTIC LIVE LIVE LOAD AS REQUIRED BY NOTES "B" AND |
| | "G" OF TABLE R301.5. NOTE: CLEARLY SPECIFY THE LOADS |
| | FOR SECOND FLOOR, ROOF, ETC. |
| | |
| | D) SPECIFY ON THE TYPICAL WALL SECTION THE MIN. HEIGHT |
| | ABOVE FINISHED GRADE AS REQUIRED BY SEC. R404.16. NOTE: |
| | SIZE OF FOUNDATION ON SHEET A-1 MAY NEED TO BE REVISED. |
| | |
| | E) SPECIFY ON THE TYPICAL WALL SECTION THE MIN. FOOTING |
| | DEPTH AS REQUIRED BY SEC. R404.16. NOTE: SIZE OF |
| | FOUNDATION ON SHEET A-1 MAY NEED TO BE REVISED. |
| | COORDINATE WITH FINISH GRADE ITEM ABOVE. |
| | |
| | F) ENGINEER OF RECORD TO SPECIFY THE ROOF TILE |
| | FASTENING SPECIFICATIONS AS REQUIRED BY SEC. 107.2.1.2 |
| | CITY AMENDMENTS. IF USING NAILS, THEN SPECIFY TYPE, |
| | SIZE AND NUMBER OF NAILS. |
| | |
| | G) REVISE ROOF SHEATHING FASTENING SPECIFICATIONS ON |
| | TYPICAL WALL SECTION. SEC. R803.2.3.1 REQUIRES RING |
| | SHANK NAILS. |
| | |
| | H) SPECIFY STUCCO THICKNESS ON THE TYP. WALL SECTION AS |
| | REQUIRED BY TABLE R702.1(1). NOTE: 7/8" MIN. FOR |
| | EXTERIOR. |
| | |
| | I) TYP. EXTERIOR WALL CONSTRUCTION SHOWN ON TYP. WALL |
| | SECTION DOESN'T MATCH LOCATION OF COLUMNS SHOWN ON |
| | PLANS. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 10- SHEET S-1: (1) NEED TO PROVIDE ENGINEER OF RECORD |
| | INFORMATION AND DRAWING NEEDS TO BE SIGNED AND SEALED. |
| | THIS SHEET CONTAINS STRUCTURAL SPECIFICATIONS. CHAPTER |
| | 471 F. S. THIS SHEET CONTAINS STRUCTURAL |
| | SPECIFICATIONS. (2) UPDATE ALL NOTES REFERENCING THE |
| | CURRENT 2014 FBC. |
| | |
| | 11- THE NAME OF THE STREET IS INCORRECT. THE CORRECT |
| | NAME IS NOTTINGHAM BLVD. REVISE ALL DRAWINGS AS |
| | REQUIRED. INCLUDING THE NAME OF THE STREET SHOWN ON THE |
| | SITE PLAN ON SHEET S-1. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 12- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | FRAMING OF THE ARCHED OPENINGS AT GARAGE DOORS AS SHOWN |
| | ON PLANS. SEC. R301. |
| | |
| | 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) GARAGE DOORS AS SHOWN ON PLANS. INFORMATION |
| | SUBMITTED DOESN'T HAVE A FLORIDA PRODUCT APPROVAL COVER |
| | PAGE OR MIAMI-DADE NOA. IF THERE IS NOT AN APPROVED |
| | PRODUCT APPROVAL, THEN MANUFACTURER MAY PROVIDE |
| | COMPLETE ENGINEERING PACKAGE FOR BUILDING OFFICIAL |
| | APPROVAL. |
| | |
| | B) ENTRY DOOR. DRAWINGS SUBMITTED FOR FLORIDA PRODUCT |
| | APPROVAL FL10975.3 WERE UPDATED FOR THE 2014 CODE |
| | VERSION. NEED TO SUBMIT THE CURRENT DRAWINGS WITH |
| | REVISION #3 DATED 1/30/15. |
| | |
| | C) SINGLE HUNG WINDOWS. INFORMATION SUBMITTED DOESN'T |
| | HAVE A FLORIDA PRODUCT APPROVAL COVER PAGE OR |
| | MIAMI-DADE NOA. IF THERE IS NOT AN APPROVED PRODUCT |
| | APPROVAL, THEN MANUFACTURER MAY PROVIDE COMPLETE |
| | ENGINEERING PACKAGE FOR BUILDING OFFICIAL APPROVAL. |
| | |
| | D) FIXED WINDOWS. INFORMATION SUBMITTED DOESN'T HAVE A |
| | FLORIDA PRODUCT APPROVAL COVER PAGE OR MIAMI-DADE NOA. |
| | IF THERE IS NOT AN APPROVED PRODUCT APPROVAL, THEN |
| | MANUFACTURER MAY PROVIDE COMPLETE ENGINEERING PACKAGE |
| | FOR BUILDING OFFICIAL APPROVAL. |
| | |
| | E) CASEMENT WINDOWS AS SHOWN ON THE WINDOW SCHEDULE. |
| | |
| | F) ROOF TILE AS SHOWN ON PLANS. |
| | |
| | G) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF |
| | RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED |
| | ADHESIVES. |
| | |
| | H) FLAT ROOF OVER NEW ENTRY. AND, CLEARLY MARK SELECTED |
| | APPROVED ASSEMBLY. IF SELECTED ASSEMBLY DOESN'T MEET |
| | THE CALCULATED DESIGN PRESSURES, THEN NEED TO SUBMIT |
| | SIGNED AND SEALED RAS 117 CALCULATIONS (IF THE SELECTED |
| | ASSEMBLY ALLOWS IT). |
| | |
| | I) SOLATUBE SKYLIGHTS AS SHOWN ON PLANS. |
| | |
| | J) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | K) WINDOW MULLIONS AS SHOWN ON PLANS. AND CLEARLY |
| | SPECIFY/MARK MULLION SIZE TO VERIFY THE DESIGN |
| | PRESSURES. |
| | |
| | L) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ROOF |
| | FRAMING PLANS AND ALL OTHER DETAILS. OR PROVIDE CURRENT |
| | FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED |
| | CONNECTOR. NOTE: REVISE PRODUCT APPROVAL NUMBER LISTED |
| | FOR CONNECTOR "E" ON SHEET A-3. |
| | |
| | 14- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REPLACE AND REMOVE ANY REVISED SHEET. SUBMIT |
| | OLD COPIES FOR REFERENCE. |
| | |