 PROJECT: 909 HENRIETTA
 PERMIT#: 15070169
 CODE: 2011 EDITION OF THE NEC, 5TH EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) WHAT IS THE PURPOSE OF THE SERVICE AND PANEL CHANGE?
 IS THIS AN UPGRADE? WHAT IS THE EXISTING SERVICE? IS
 THERE NEW EQUIPMENT TO BE INSTALLED? INDICATE ANY NEW
 EQUIPMENT TO BE INSTALLED.
  
 2) PROVIDE A PANEL SCHEDULE FOR EACH PANEL. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 3) PROVIDE A SITE PLAN THAT INDICATES THE LOCATION OF
 THE SERVICE OUTSIDE AND A FLOOR PLAN THAT INDICATES THE
 LOCATION OF THE PANEL INSIDE.
  
 4) INDICATE THE CONTENTS OF EACH CONDUIT. THE SERVICE
 ENTRANCE CONDUIT IS SHOWN AS A 2" RIDGED WITH 3, #1/0.
 WHAT IS THE FEEDER BETWEEN THE MAIN AND THE PANEL?
  
 5) VERIFY OR INDICATE THE EXISTANCE OR INSTALLATION OF
 INTERCONNECTED SMOKE DETECTORS AS REQUIRED FOR NEW
 CONSTRUCTION. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  