| Plan Review Notes For Permit 15070145 |
| Permit Number |
15070145 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-11-10 18:47:27 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRIC | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PAPER PLANS AND DOCUMENTS THAT ARE SUBMITTED FOR | | | PUBLIC RECORD ARE REQUIRED TO BE SIGNED, SEALED AND | | | DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE | | | CHARGE. THE ENGINEER'S HANDWRITTEN SIGNATURE IS | | | REQUIRED ( FACSIMILES ARE NOT ACCEPTABLE). THE SEAL | | | SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND | | | COMPLY WITH FAC 61G15-23.001. DIGITAL SEALS AND | | | SIGNATURES CAN ONLY BE USED FOR ELECTRONICALLY | | | TRANSMITTED PLANS AND OTHER DOCUMENTS. FS 471, FAC | | | 61G15-23.002 AND FAC 61G15-23.003 | | | |
|