| 2015-11-10 09:51:58 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) PAPER PLANS AND DOCUMENTS THAT ARE SUBMITTED FOR |
| | PUBLIC RECORD ARE REQUIRED TO BE SIGNED, SEALED AND |
| | DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE |
| | CHARGE. THE ENGINEER'S HANDWRITTEN SIGNATURE IS |
| | REQUIRED ( FACSIMILES ARE NOT ACCEPTABLE). THE SEAL |
| | SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND |
| | COMPLY WITH FAC 61G15-23.001. DIGITAL SEALS AND |
| | SIGNATURES CAN ONLY BE USED FOR ELECTRONICALLY |
| | TRANSMITTED PLANS AND OTHER DOCUMENTS. FS 471, FAC |
| | 61G15-23.002 AND FAC 61G15-23.003 |
| | |
| | 2) SHOW COMPLIANCE WITH FBC R401.3 FOR SURFACE |
| | DRAINAGE. SEE COMMENT #5 FROM FIRST REVIEW. |
| | |
| | 3) PROVIDE A SECTIONAL GARAGE DOOR BUCK DETAIL. |
| | INDICATE THE SPECIFIC ANCHORS AND SPACING. FBC 107.2.1 |
| | & FBC-R612.7.2 |
| | |
| | 4) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | WAYNE DALTON GARAGE DOOR HAS DESIGN PRESSURES OF +30.0 |
| | , -33.50 PSF AND THE PLANS REQUIRE +37.30, -45.70 PSF. |
| | |
| | 5) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | THERMA TRU GLAZED OUTSWING STEEL DOOR FL7586.1 HAS |
| | DESIGN PRESSURES OF + 47.0, -47.0 PSF AND THE PLANS |
| | REQUIRE +41.24, -53.58 PSF. |
| | |
| | 6) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD FOR THE PEEL AND STICK ROOFING TILE UNDERLAYMENT |
| | AS REQUIRED BY DCA RULE 9N-3 & FBC 107.3.4.1. |
| | |
| | 7) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD FOR THE ROOFING MATERIAL FOR THE GARAGE ROOF |
| | FLAT DECK AS REQUIRED BY DCA RULE 9N-3 & FBC 107.3.4.1. |
| | |
| | 8) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| | TO INSTALL THE CEMENT ROOF TILE AND RESIST THE OVERTURN |
| | MOMENT. IF AN ADHESIVE IS USED, SUBMIT THE PRODUCT |
| | APPROVALS FOR IT. FBC 107.2.1 & FBC-R905.3 |
| | |
| | 9) R905.11.1 SLOPE. MODIFIED BITUMEN MEMBRANE ROOFS |
| | SHALL HAVE A DESIGN SLOPE OF A MINIMUM OF ONE-FOURTH |
| | UNIT VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) |
| | FOR DRAINAGE. (GARAGE) SPECIFY THE SLOPE ON THE PLANS. |
| | |
| | 10) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |