| 2015-09-09 09:26:40 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) / 2011 NEC |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY ELECTRICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON |
| | JUNE 30, 2015. THE PERMIT APPLICATION FOR THIS PROJECT |
| | WAS SUBMITTED ON JULY 6, 2015. UPDATE REFERENCES TO THE |
| | 2010 FBC TO THE 2014 FBC. |
| | |
| | 2) THE PLANS DO NOT INDICATE HOW THE ELECTRIC WILL BE |
| | SUPPLIED TO THE DETACHED GARAGE. PROVIDE ALL DETAILS, |
| | WIRE SIZES, CONDUIT SIZE, DISCONNECTS, PANEL LOCATIONS, |
| | PANEL SCHEDULES, ETC. TO SHOW COMPLIANCE WITH THE 2011 |
| | NEC. INCLUDING DISCONNECT, PANEL SCHEDULES, ETC. FBC |
| | 107.2.1 |
| | |
| | 3) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER |
| | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2 |
| | FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN |
| | THAT SPACE. THE COUNTERTOP SPACE ACROSS FROM THE PANTRY |
| | DOES NOT HAVE ANY RECEPTACLE OUTLETS SPECIFIED ON THE |
| | PLANS. |
| | |
| | 4) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME |
| | POINTS ALONG THE WALL SPACE EXCEED 6' FROM AN OUTLET |
| | AND SOME USEABLE WALL SPACES 2 FT OR MORE IN WIDTH ARE |
| | MISSING THE REQUIRED RECEPTACLE OUTLETS. |
| | |
| | 5) THE ELECTRICAL RISER DOES NOT MATCH THE FLOOR PLAN. |
| | THE FLOOR PLAN HAS A 200 AMP SUB-PANEL IN A CLOSET ON |
| | THE FIRST FLOOR AND ANOTHER 200 AMP SUB-PANEL LOCATED |
| | IN THE HALL ON THE SECOND FLOOR. PLEASE CLARIFY. NEC |
| | 240.24 (D) ELECTRICAL PANELS SHALL NOT BE LOCATED IN |
| | THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS |
| | CLOTHES CLOSETS. |
| | |
| | 6) FBC 107.2.1 IT APPEARS FROM THE MECHANICAL PLANS |
| | THAT THE AIR HANDLER IS LOCATED IN THE ATTIC. SHOW THE |
| | LOCATION OF THE AHU ON THE ELECTRICAL PLANS. NEC 440.11 |
| | & 440.14 SHOW THE LOCATION OF THE REQUIRED A/C |
| | EQUIPMENT DISCONNECTING MEANS ON THE PLANS. NEC 210.63 |
| | - PROVIDE A GFCI PROTECTED SERVICE OUTLET FOR WITHIN |
| | 25' OF MECHANICAL EQUIPMENT. NEC 110.26 SUFFICIENT |
| | ACCESS AND WORKING SPACE SHALL BE PROVIDED AND |
| | MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT |
| | READY AND SAFE OPERATION AND MAINTENANCE OF SUCH |
| | EQUIPMENT. NEC 210.70 (A)(3) PROVIDE A SWITCHED |
| | LIGHTING OUTLET AT OR NEAR THE EQUIPMENT. NEC 110.33 |
| | (B) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO |
| | GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL |
| | EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR |
| | MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES. |
| | |
| | 7) NEC 210.8(A)(2) THE GARAGE DOOR OPENER RECEPTACLE |
| | OUTLETS ARE REQUIRED TO BE GFCI PROTECTED. |
| | |
| | 8) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| | REQUIRED. |
| | |
| | 9) NEC 110.3 (B) SMOKE ALARMS AND CARBON MONOXIDE |
| | ALARMS SHALL BE INSTALLED IN ACCORDANCE WITH THEIR |
| | LISTINGS OR LABELING AND PER MANUFACTURER'S |
| | INSTRUCTIONS IN ORDER TO INSURE OPTIMUM COVERAGE. |
| | |
| | |
| | |
| | |
| | |
| | |