| Notes |
| Date |
Text |
| 2015-07-08 20:08:58 | ELECTRICAL PROVISOS FOR PERMIT 15070113: | | | PER NEC 314.27 CEILING OR WALL OUTLET INTENDED FOR | | | LUMINAIRE SHALL BE LISTED TO SUPPORT 50LB. | | | PER NEC 210.52 D, YOU SHALL HAVE A GFCI OUTLET WITHIN | | | 3FT. OF THE BATHROOM SINK. (SAME OR ADJACENT WALL) | | | PER NEC 410.10D, LUMINAIRES DIRECTLY ABOVE SHOWER OR | | | TUB SHALL BE LISTED FOR WET LOCATION | | | PER NEC 404.2, UNLESS WORK IS IN CONDUIT WITH AMPLE | | | SPARE ROOM, A NEUTRAL SHALL BE RUN TO EVERY SWITCH | | | |
|