 PROJECT: YOUNG. PERGOLA ELECTRICAL
 PERMIT#: 15070104
 CODE: 2011 EDITION OF THE NEC, 5TH EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE ADDITIONAL INFORMATION INDICATING THE ACTUAL
 DIMENSION OF THE NEW RECEPTACLES PROPOSED TO BE
 INSTALLED NEAR THE EDGE OF THE POOL. RECEPTACLES SHALL
 BE NOT LESS THAN 6 FT FROM THE INSIDE WALLS OF A POOL
 AND SHALL BE GFI PROTECTED. SEE .NEC 680.22(A)(2) AND
 NEC 680.22(A)(4)
  
 2) PROVIDE ADDITIONAL INFORMATION INDICATING THE ACTUAL
 DIMENSION OF THE NEW CEILING FAN OUTLETS PROPOSED TO BE
 INSTALLED NEAR THE EDGE OF THE POOL. IN OUTDOOR POOL
 AREAS, LUMINAIRES, LIGHTING OUTLETS, AND
 CEILINGSUSPENDED (PADDLE) FANS INSTALLED ABOVE THE POOL
 OR THE AREA EXTENDING 5 FT HORIZONTALLY FROM THE INSIDE
 WALLS OF THE POOL SHALL BE INSTALLED AT A HEIGHT NOT
 LESS THAN12 FT ABOVE THE MAXIMUM WATER LEVEL. NEC
 680.22(B)(1) AND 680.22(B)(4)
  
 3) PROVIDE ADDITIONAL INFORMATION INDICATING THE
 LOCATION OF THE SOURCE OF POWER AND WIRING METHOD FOR
 THE NEW RECEPTACLES AND CEILING FAN OUTLETS. WPB
 AMENDMENTS TO THE FBC 107.2.1
  
 4) PROVIDE ADDITIONAL INFORMATION INDICATING HOW THE
 CEILING FANS ARE PROPOSED TO BE CONTROLLED. SEE NEC
 680.22(C)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  