2015-10-08 11:50:412ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070097
 10/8/15
  
 1) IN RESPONSE TO THE PREVIOUS COMMENTS REGARDING AC IN
 UNITS 402 & 404, TWO SETS OF ENERGY AND AN AC LOAD
 SUMMARY HAVE BEEN SUBMITTED FOR UNIT 402, BUT NONE HAVE
 BEEN SUBMITTED FOR 404. THE CALCULATIONS SUBMITTED FOR
 402 INDICATE A 16 SEER SYSTEM, HOWEVER THE PLAN IS
 INDICATING A 13 SEER SYSTEM. ADDITIONALLY THE MODEL
 MUMBERS ON THE PLAN DON'T MATCH THE MODEL NUMBERS ON
 THE LOAD SUMMARY: PLEASE CORRECT. PLEASE NOTE THAT THE
 AC SUMMARY CALCS MUST HAVE THE MANUAL J WORKSHEETS
 ATTACHED FOR COMPLETE REVIEW.
 2) THIS IS THE SECOND REQUEST FOR A MECHANICAL
 SUB-PERMIT AND ADJUSTED PERMIT VALUE INCREASE FOR THE
 COST OF THE AC SYSTEM- LABOR, MATERIALS, AND EQUIPMENT.
  