2015-10-19 08:03:24BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070097
 ADD: 402 & 404 50TH ST.
 CONT: BMB SOLUTIONS
 TEL: (561)503-1415
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, RESIDENTIAL.
  
 2ND REVIEW
 DATE: MON. OCT. 19/2015
 ACTION: DENIED
  
 1) 2ND REQUEST. THE VALUE ASSESSED TO THE PROJECT IS
 EXTREMELY LOW FOR THE VALUE OF THE PROJECT. THE VALUE
 OF THE WINDOW REPLACEMENT ALONE IS BETWEEN $20,000.00
 TO $25,000.00 FOR THE REPLACEMENT OF WINDOWS AND DOORS
 ALONE. SINCE THERE ARE SUB-PERMITS WITHIN THE PACKAGE
 THE VALUE FOR THE MEP PERMITS ARE ALSO TO BE ADDED TO
 THE VALUE OF THE MASTER PERMIT. NOTE THE IMPROVEMENT
 VALUE OF THIS PROPERTY IS $69,305.00.
 $69,305 X 0.30 = $ 20,791.50.
  
 PERMIT FEES/ PLAN REVIEW:
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS PERMIT IS FOR THE REMOVAL AND INSTALATION OF 22
 WINDOWS, 8 MULLIONS AND 4 EXTERIOR DOORS. QUOTE
 SUBMITTED IS FOR 11 WINDOWS ONLY. IT DOES NOT APPEAR TO
 BE FOR THIS LOCATION, ONLY (1) WINDOW IS SIZED FOR A
 EGRESS WINDOW. NO MULLIONS NOR EXTERIOR DOORS.
  
 2) COMPLIED. THE PLANS INDICATE THEY WERE DESIGNED TO
 THE 2010 FBC, THE 5TH EDITION OF THE FBC WAS ADOPTED
 STATE WIDE JUNE 30, 2015. PLEASE UPDATE PLANS AND
 REQUIREMENTS INCLUDING THE WIND DESIGN.
  
 3) COMPLIED. UNDER THE 2014 FBC-EXISTING BUILDING 706.4
 WHEN REPLACING MORE THAN 25% OF THE GLAZED AREA OF
 GLAZING THE WINDOWS AND DOORS NEED TO MEET THE
 REQUIREMENTS OF LARGE MISSILE IMPACT GLAZING OR
 APPROVED STORM SHUTTERS.
  
 4) COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) COMPLIED. COMPONENTS & CLADDING 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING, FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS. NOT REVIEWED BY THE DESIGNER OF
 RECORD.
 (B) WINDOWS & MULLIONS, MCY ENGINEERING. WAS NOT
 SUBMITTED WITH A FLORIDA OR MIAMI-DADE COVER SHEET. NOT
 REVIEWED BY THE DESIGNER OF
 RECORD.
 (E) STORM SHUTTERS (IF THE GLAZED OPENINGS DO NOT HAVE
 LARGE MISSILE IMPACT TESTING)
  
 6) COMPLIED. SHEET1.1 & 2.1 BOTH SHOW A CORNER POST
 WITH WINDOWS ON BOTH SIDES, PLEASE PROVIDE WHAT TYPE OF
 FRAMING SYSTEM THIS CORNER POST IS CONSISTED OF AND HOW
 DOES IT CONNECT TO THE MWFRS MAIN WIND FORCE RESISTING
 SYSTEM.
  
 7) 2ND REQUEST. 2014 EXISTING BUILDING CODE, 707.1.
 MINIMUM REQUIREMENTS. ALTERATION SUBJECT TO THIS
 CHAPTER SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, ENERGY CONSERVATION.
  
 2014 ENERGY CODE DEFINITIONS: RENOVATED BUILDINGS.
 ARESIDENTIAL BUILDING UNDERGOING ALATERATIONS THAT
 VARIES OR CHANGES INSULATION, HVAC SYSTEMS WATER
 HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS,
 PROVIDED THE ESTIMATE COST OF RENOVATION EXCEEDS 30
 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE. SEE
 COMMENT # 1, 30% OF THE APPRAISED IMPROVEMENT VALUE OF
 THE STRUCTURE IS $20,791.50.
  
 PLEASE REVIEW 2014 FBC-ENERGY CODE R101.4.3 ALTERATIONS
 AND TABLE R402.1.1 INSULATION & FENESTRATIONS
 REQUIREMENTS BY COMPONENT. NOTE FOR ZONE # 1 THE
 FENESTRATION U-FACTOR OF 0.65 AND GLAZED FENESTRATION
 SHGC OF 0.25. THE DESIGNER MAY LOOK AT THIS AS
 PRESCRIPTIVE OR PREFORMANCE BASED.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  