Plan Review Notes
Plan Review Notes For Permit 15070097
Permit Number 15070097
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-17 11:45:541ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070097
  
 1) SHEET 3.1.: PROVIDE A SCOPE OF WORK OUTLINE FOR AC
 ON THE PLAN. CLARIFY IF THE SYSTEMS SHOWN ARE: A) EXACT
 SAME SIZE, SAME LOCATION REPLACEMENTS OF EQUIPMENT AND
 COMPONENTS. B) LARGER CAPACITY EQUIPMENT UPGRADES. C)
 EQUIPMENT REPLACEMENTS WITH RELOCATIONS. PLEASE NOTE
 THAT EQUIPMENT SIZING CALCULATIONS FOR COOLING AND
 HEATING EQUIPMENT SIZING ARE REQUIRED FOR EITHER ITEMS
 SYSTEM SIZING INCREASE, OR EQUIPMENT RELOCATIONS.
 2. SHEET 3.1: PROVIDE AC EQUIPMENT SCHEDULES ON THE
 PLANS INDICATING MAKES AND MODELS OF AIR HANDLERS AND
 CONDENSERS, COOLING AND HEATING CAPACITIES, EFFIENCY
 RATINGS, ELECTRIAL DATA ETC.
 3. SHEET 3.1: INDICATE THE DIMENSIONS OF THE R/A AND
 T/A GRILLS SHOWN ON THE PLAN. NOTE: THE T/A GRILLS ARE
 ACTUALLY BEING USED AS R/A GRILLS: PLEASE CORRECT.
 4. SUBMIT A MECHANICAL SUB-PERMIT APPLICATION, AND ADD
 THE COST OF THE AC WORK TO THE TOTAL PROJECT VALUE ON
 THE PERMIT APPLICATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER