| 2015-07-17 11:45:54 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15070097 | | | | | | 1) SHEET 3.1.: PROVIDE A SCOPE OF WORK OUTLINE FOR AC | | | ON THE PLAN. CLARIFY IF THE SYSTEMS SHOWN ARE: A) EXACT | | | SAME SIZE, SAME LOCATION REPLACEMENTS OF EQUIPMENT AND | | | COMPONENTS. B) LARGER CAPACITY EQUIPMENT UPGRADES. C) | | | EQUIPMENT REPLACEMENTS WITH RELOCATIONS. PLEASE NOTE | | | THAT EQUIPMENT SIZING CALCULATIONS FOR COOLING AND | | | HEATING EQUIPMENT SIZING ARE REQUIRED FOR EITHER ITEMS | | | SYSTEM SIZING INCREASE, OR EQUIPMENT RELOCATIONS. | | | 2. SHEET 3.1: PROVIDE AC EQUIPMENT SCHEDULES ON THE | | | PLANS INDICATING MAKES AND MODELS OF AIR HANDLERS AND | | | CONDENSERS, COOLING AND HEATING CAPACITIES, EFFIENCY | | | RATINGS, ELECTRIAL DATA ETC. | | | 3. SHEET 3.1: INDICATE THE DIMENSIONS OF THE R/A AND | | | T/A GRILLS SHOWN ON THE PLAN. NOTE: THE T/A GRILLS ARE | | | ACTUALLY BEING USED AS R/A GRILLS: PLEASE CORRECT. | | | 4. SUBMIT A MECHANICAL SUB-PERMIT APPLICATION, AND ADD | | | THE COST OF THE AC WORK TO THE TOTAL PROJECT VALUE ON | | | THE PERMIT APPLICATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|