Plan Review Notes
Plan Review Notes For Permit 15070058
Permit Number 15070058
Review Stop B
Sequence Number 5
Notes
Date Text
2016-02-10 11:32:15****PROVISOS****
 ****REVISION REQUIRED PRIOR TO DECK FLOOR
 INSTALLATION****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLAN PREPARED BY VJ GERLEY, PE DATED 2/5/2016:
  
 1. FBC 107.2.1: CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS ...
  
 IN ORDER FOR AN ACCURATE REVIEW TO BE PERFORMED,
 PROVIDE BASIC INFORMATION ABOUT THE EXISTING BUILDING:
 OCCUPANCY CLASSIFICATION FBC CHAPTER 3, BUILDING TYPE
 FBC CHAPTER 5.
  
 2. FBC 5TH EDITION EXISTING BUILDING 301.1, APPLICANT
 IS TO ELECT THE METHOD OF COMPLIANCE. REVISE PLAN TO
 INDICATE METHOD SELECTED. COMPLETE CODE REFERENCES
 CANNOT BE PROVIDED WITHOUT THIS INFORMATION.
  
 3. SCOPE NOT CLEAR. SECTION 1-6 STATES THAT ELECTRICAL
 WIRING MAY BE REUSED BUT NO ELECTRICAL PLAN WAS
 SUBMITTED, NO ELECTRICAL APPLICATION SUBMITTED, FBC
 107.
  
 4. REGARDING THE PARTITION WALLS, NO SPECIFICATION
 (OTHER THAN "REPLACE WITH REPAIR EQUAL TO EXISTING")
 WAS PROVIDED. THIS IS A WALL SUBJECT TO WIND LOADS.
 BUILDING "E" ELEVATION INDICATES THAT THE WALL IS TO
 REMAIN.
  
 ALL OF THE DETAIL NUMBERS HAVE BEEN REMOVED. THERE ARE
 SOME REFERENCES TO DETAILS BUT THE DETAILS THEMSELVES
 ARE NOT IDENTIFIED, FBC 107.
  
 FIRST FLOOR CMU PARTITION WALL DOES NOT APPEAR IN
 PHOTOGRAPHS OF THE EXISTING BUILDING, PLAN INDICATES
 REPLACEMENT IF NECESSARY, REVISE TO PROPOSE NEW OR
 REMOVE.
  
 5. THE PLAN IS NOT CLEAR AS TO SCOPE, FBC 107. BUILDING
 ORIENTATION HAS NOT BEEN INDICATED, DETAILS DO NOT
 CORRELATE WITH PLAN OR ELEVATIONS.
  
 6. FBC 1609, SECTION 1-12 STATES "WIND PRESSURES
 DESIGNED FOR OPEN STRUCTURE", BUT THIS STRUCTURE DOES
 NOT MEET THE DEFINITION OF OPEN, SEE FBC 1609,
 ASCE7-10, CHAPTER 26. REVISE ENCLOSURE CLASSIFICATION
 AND REVISE OTHER DETAILS AS APPLICABLE OR CLARIFY.
  
 7. MEAN ROOF HEIGHT IS GIVEN AS 24 FEET. BUILDING 'E'
 ELEVATION DEPICTS THREE STORIES AND A PITCHED ROOF.
 SECTION C SPECS A 12IN FLOOR JOIST. IT APPEARS THAT 24
 FEET IS NOT AN ACCURATE MRH FOR THIS STRUCTURE AS IT IS
 26FT FROM FINISHED FLOOR TO UNDERSIDE OF ROOF TRUSSES,
 NO DIMENSION PROVIDED FOR THE ROOF. EITHER CORRECT THE
 MRH OR PROVIDE INFORMATION TO CLARIFY THE STATED MRH OF
 24FT.
  
 8. FBC 1809.4, TYPICAL WALL SECTION DOES NOT SPECIFY
 DEPTH OF FOUNDATION RELATIVE TO GRADE, REVISE.
  
 9. BALCONY DESIGN LOADS NOT SPECIFIED, PLEASE REVISE,
 FBC 107.
  
 10. RAILING ENGINEERING IS A PHOTOCOPY AND NOT REVIEWED
 BY ENGINEER OF RECORD AS REQUIRED FOR DELEGATED
 ENGINEERING, FAC61G. PROVIDE SIGNED, SEALED, DATED
 ORIGINAL ENGINEERING WITH THE REVISED PLAN.
  
 11. ELEVATIONS AND SECTIONS ARE NOT MARKED RELATIVE TO
 DIRECTION. SECTION 3 APPEARS TO BE THE REAR (BASED ON
 ROOF ORIENTATION). IF THIS IS A SECTION WHICH
 REPRESENTS THE REAR, CONSTRUCTION/REPAIR OF THE
 CANTILEVER TO THE SIDES IS NOT CLEAR. IT APPEARS THAT
 NO REPAIR DETAIL WAS PROVIDED FOR THE SECOND FLOOR LEFT
 AND RIGHT SIDE CANTILEVERED BALCONY AREAS, FBC 107.
  
 12. A FLASHING SPECIFICATION PROVIDED, BUT TYPICAL WALL
 SECTION AND UNNUMBERED SECTION (PREVIOUSLY SECTION 3)
 GRAPHICALLY APPEAR TO DEPICT FLASHING ON THE SECOND
 FLOOR, BUT NOT ON THE THIRD FLOOR. FBC 1403.2, REVISE
 PLAN TO EITHER INCLUDE FLASHING ON THE THIRD FLOOR OR
 PROVIDE DETAILS TO CLARIFY HOW AN INSTALLATION WHICH
 LACKS FLASHING WILL NOT COMPROMISE THE WATER RESISTANCE
 OF THE EXTERIOR WALL.
  
 13. THE WIND INFORMATION SPECIFIES "OVERHANGS" DESIGN
 PRESSURE OF -0 FOR ZONE 1. IS "OVERHANGS" THE
 BALCONIES? PROVIDE CALCULATIONS FOR THE NEGATIVE
 PRESSURE OF -0 FOR ZONE 1, FBC 1609.
  
 14. FBC 107, PLAN SPECIFIES HARDIBOARD SOFFITS, SECTION
 6-2 SPECIFIES PLYWOOD, CLARIFY. REMOVE ANY OTHER
 DISCREPANCIES FROM THE PLAN.
  
 15. ENGINEER SPECIFIES DECTEC OVER 3/4" PLYWOOD.
  
 SEE DECTEC PRODUCT APPROVAL, 5/8" TONGUE AND GROOVE
 PLYWOOD GLUED WITH LEPAGE BULLDOG GRIP PL 400 HEAVY
 DUTY SUB FLOOR ADHESIVE, #8 WOOD SCREWS AT 6" OC
 REQUIRED. THIS ASSEMBLY HAS A DESIGN PRESSURE
 LIMITATION OF -135PSF. ZONE 3 ON THE PLAN HAS A DESIGN
 PRESSURE REQUIREMENT OF -137.2. IT IS NOT CLEAR WHY THE
 ENGINEER SPECIFIES A PRODUCT WHICH DOES NOT MEET THE
 DESIGN PRESSURES SPECIFIED BY HIM. EXISTING BALCONY
 FLOOR JOIST SPACING IS NOT STATED ON THE SECTIONS SO IT
 IS NOT CLEAR IF THE EXISTING CONDITIONS COMPLY WITH THE
 24IN OC REQUIREMENT.
  
 THIS DISCREPANCY (TONGUE AND GROOVE VS. STANDARD),
 JOIST SPACING, AND DESIGN PRESSURE LIMITATION OF THE
 DECTEC IS TO BE RESOLVED PRIOR TO INSTALLATION OF THE
 BALCONY FLOORS. A SITE SPECIFIC PRODUCT APPROVAL CAN BE
 CONSIDERED SUBJECT TO INFORMATION (ENGINEERING
 RATIONALE), COMPARATIVE ANALYSIS, ETC. PROVIDED BY
 ENGINEER.
  
 16. THE ARTISAN LAP SIDING NOA IS FOR SIDING AND DOES
 NOT INCLUDE INFORMATION FOR FASCIA INSTALLATION.
 PROVIDE THE APPLICABLE PRODUCT APPROVAL, REVIEWED BY
 DESIGNER OF RECORD, FBC 1609, FBC 107.
  
  
  