Plan Review Notes
Plan Review Notes For Permit 15070058
Permit Number 15070058
Review Stop B
Sequence Number 3
Notes
Date Text
2015-12-17 18:05:55****CORRECTIONS****
 ****UPDATED ON 1/26/2016****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLAN PREPARED BY **REDACTED** DATED 11/16/15:
  
 1. FBC 107.2.1: CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS ...
  
 IN ORDER FOR AN ACCURATE REVIEW TO BE PERFORMED,
 PROVIDE BASIC INFORMATION ABOUT THE EXISTING BUILDING:
 OCCUPANCY CLASSIFICATION FBC CHAPTER 3, BUILDING TYPE
 FBC CHAPTER 5.
  
 2. FBC 5TH EDITION EXISTING BUILDING 301.1, APPLICANT
 IS TO ELECT THE METHOD OF COMPLIANCE. REVISE PLAN TO
 INDICATE METHOD SELECTED. COMPLETE CODE REFERENCES
 CANNOT BE PROVIDED WITHOUT THIS INFORMATION.
  
 3. SCOPE NOT CLEAR. SECTION 1-6 STATES THAT ELECTRICAL
 WIRING MAY BE REUSED BUT NO ELECTRICAL PLAN WAS
 SUBMITTED, NO ELECTRICAL APPLICATION SUBMITTED, FBC
 107.
  
 4. SOME STATEMENTS ON THE PLAN ARE NOT CLEAR AS TO
 MEANING. FOR INSTANCE, ITEM 1-4, "NEW BALCONY DECKING
 AND ALUMINUM RAILING, THIS DOES NOT QUALIFY EXISTING
 JOIST INTEGRITY." DESIGNER'S INTENT IS NOT CLEAR,
 PLEASE REVISE TO CLARIFY.
  
 ALSO SEE SECTION 3 "INSPECTION OF EXTIN'G CANTILEVER WD
 JST WITH ROT (STRUCTURAL INTEGRITY):" AND THEN PROVIDES
 A SPEC FOR REPAIR. DESIGNER'S INTENT NOT CLEAR, PLEASE
 REVISE TO CLARIFY.
  
 SECTION 3 "NON-BRG EXIST SEPARATION WALLS W/ROT SHALL
 REPLACE WITH REPAIR EQUAL TO EXISTING." NO
 SPECIFICATION (OTHER THAN "REPLACE WITH REPAIR EQUAL TO
 EXISTING") WAS PROVIDED. THIS IS A WALL SUBJECT TO WIND
 LOADS. BUILDING "E" ELEVATION INDICATES THAT THE WALL
 IS TO REMAIN. SCOPE NOT CLEAR, FBC 107.
  
 NOTE 1-6 "NO STRUCTURAL REMOVAL AS INDICATED ON THE
 DRAWINGS."
  
 5. THE PLAN IS NOT CLEAR AS TO SCOPE, FBC 107. BUILDING
 "E" ELEVATION AND SECTION 3 AND ADJACENT ELEVATION
 INCLUDE ELEMENTS WHICH ARE NOT CLEAR AS TO WHETHER THEY
 ARE EXISTING OR ARE TO BE REPLACED, PLEASE REVISE TO
 CLEARLY DEPICT SCOPE.
  
 6. FBC 1609, SECTION 1-12 STATES "WIND PRESSURES
 DESIGNED FOR OPEN STRUCTURE", BUT THIS STRUCTURE DOES
 NOT MEET THE DEFINITION OF OPEN, SEE FBC 1609,
 ASCE7-10, CHAPTER 26. REVISE ENCLOSURE CLASSIFICATION
 AND REVISE OTHER DETAILS AS APPLICABLE OR CLARIFY.
  
 7. MEAN ROOF HEIGHT IS GIVEN AS 24 FEET. BUILDING 'E'
 ELEVATION DEPICTS THREE STORIES AND A PITCHED ROOF.
 SECTION C SPECS A 12" FLOOR JOIST. IT APPEARS THAT 24
 FEET IS NOT AN ACCURATE MRH FOR THIS STRUCTURE AS IT IS
 26' FROM FINISHED FLOOR TO UNDERSIDE OF ROOF TRUSSES,
 NO DIMENSION PROVIDED FOR THE ROOF. EITHER CORRECT THE
 MRH OR PROVIDE INFORMATION TO CLARIFY THE STATED MRH OF
 24'.
  
 8. FBC 1809.4, TYPICAL WALL SECTION DOES NOT SPECIFY
 DEPTH OF FOUNDATION RELATIVE TO GRADE, REVISE.
  
 9. HARDIPLANK SPECIFIED; FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9N-3, FBC 1609. PRODUCT APPROVALS
 ARE TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL.
  
 10. CEILING FINISHED ARE TO BE REMOVED, BUT NOT
 REPLACED. PLAN INDICATES THAT THE EXISTING JOIST WILL
 REMAIN. IT APPEARS THAT THE PREVIOUS DESIGN INCLUDED AN
 ENCLOSED JOIST, THE PROPOSED DESIGN IS FOR OPEN, BUT NO
 INFORMATION REGARDING THE EXISTING JOIST WAS PROVIDED
 (SUCH AS TYPE OF LUMBER, PT). FOR JOISTS WHICH DID NOT
 ROT, THEY ARE TO REMAIN, BUT THE PLAN IS NOT CLEAR AS
 TO WHETHER OR NOT THE JOISTS WERE DESIGNED TO BE IN
 DIRECT CONTACT WITH THE ELEMENTS, FBC 107.
  
 11. BALCONY DESIGN LOADS NOT SPECIFIED, PLEASE REVISE,
 FBC 107.
  
 12. NEW RAILINGS ARE PROPOSED BUT NO STRUCTURAL
 SPECIFICATION (DESIGN LOADS, INSTALLATION SPEC, ETC.)
 PROVIDED, FBC 107.
  
 13. ELEVATIONS AND SECTIONS ARE NOT MARKED RELATIVE TO
 DIRECTION. SECTION 3 APPEARS TO BE THE REAR (BASED ON
 ROOF ORIENTATION). IF THIS IS A SECTION WHICH
 REPRESENTS THE REAR, CONSTRUCTION/REPAIR OF THE
 CANTILEVER TO THE SIDES IS NOT CLEAR. IT APPEARS THAT
 NO REPAIR DETAIL WAS PROVIDED FOR THE SECOND FLOOR LEFT
 AND RIGHT SIDE CANTILEVERED BALCONY AREAS, FBC 107.
  
 14. NO FLASHING DETAIL(S) PROVIDED, FBC 107. TYPICAL
 WALL SECTION AND SECTION 3 GRAPHICALLY APPEAR TO DEPICT
 FLASHING ON THE SECOND FLOOR, BUT NOT ON THE THIRD
 FLOOR. FBC 1403.2, REVISE PLAN TO EITHER INCLUDE
 FLASHING DETAILS OR PROVIDE DETAILS TO CLARIFY HOW AN
 INSTALLATION WHICH LACKS FLASHING WILL NOT COMPROMISE
 THE WATER RESISTANCE OF THE EXTERIOR WALL.
  
 15. I WAS UNABLE TO FIND A SPECIFICATION FOR THE NAILS
 OTHER THAN SIZE. ARE THEY COMMON HOT DIPPED GALVANIZED,
 OR STAINLESS, OR ANOTHER TYPE?
  
 ****NEW COMMENT ON 1/26/2016****
  
 16. BASED ON A CONVERSATION WITH THE CONTRACTOR, THE
 EXISTING BALCONY FLOOR JOISTS ARE NON TREATED SPRUCE
 LUMBER. AS THE NEW DESIGN PROPOSED TO EXPOSE THE
 INTERIOR GRADE LUMBER TO THE ELEMENTS, IT APPEARS THAT
 THIS DESIGN DOES NOT COMPLY WITH THE MINIMUM
 REQUIREMENTS OF THE FLORIDA BUILDING CODE. IT APPEARS
 THAT AN ALTERNATIVE DESIGN SHOULD BE CONSIDERED. PLEASE
 CONTACT ME IF YOU WISH TO DISCUSS.
  
  
  
  