Plan Review Notes
Plan Review Notes For Permit 15070056
Permit Number 15070056
Review Stop B
Sequence Number 2
Notes
Date Text
2015-08-18 08:57:59****CORRECTIONS****
  
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. APPLICATION IS TO "REMOVE & REPLACE (5) WINDOWS ON
 SECOND FLOOR, SIDING & FRAMING REPAIRS NEEDED."
  
 PER OWNER, CONTRACTOR, AND PLAN, WINDOW REPLACEMENT IS
 INCLUDED IN THE SCOPE OF ANOTHER PERMIT BY ANOTHER
 CONTRACTOR.
  
 AS THIS IS PART OF THE WINDOW RENOVATION PERMIT
 (WINDOWS CANNOT BE INSTALLED WITHOUT STRUCTURAL FRAMING
 REPAIRS, REPAIRS CANNOT BE COMPLETED WITHOUT
 INSTALLATION OF WINDOWS), THIS SHOULD HAVE BEEN
 SUBMITTED AS A REVISION TO THE MASTER PERMIT.
  
 IF THE CONTRACTOR OF THIS PERMIT (15050961, GEORGE J.
 CASTLE CONSTRUCTION) THEN WOULD LIKE TO SUB CONTRACT
 THIS PORTION OF THE WORK TO ANOTHER CONTRACTOR (ABACOA
 CONSTRUCTION), THE OTHER CONTRACTOR SHOULD SUBMIT A
 PERMIT APPLICATION AS A SUBCONTRACTOR TO THE MASTER
 PERMIT. THE OWNER CANNOT SUBCONTRACT THESE TWO PORTIONS
 OF WORK TO TWO DIFFERENT UNRELATED CONTRACTORS; THIS IS
 CONSIDERED CONTRACTING PER FS 553.
  
 PLEASE DISCUSS WITH THE CONTRACTOR (GEORGE J. CASTLE
 CONSTRUCTION) WHO HAS AN OPEN PERMIT ON THIS PROPERTY.
 COMPLETE A REVISION FORM AND THE SAME NUMBER (15070056)
 WILL BE RETAINED. DETERMINE WHETHER THE CONTRACTOR
 (GEORGE J. CASTLE CONSTRUCTION) WOULD LIKE A STRUCTURAL
 SUB PERMIT ISSUED TO ABACOA CONSTRUCTION OR IF THIS
 WILL BE INCLUDED UNDER THE SCOPE OF THE PERMIT ALREADY
 ISSUED (15050961).
  
  