| Plan Review Notes For Permit 15070056 |
| Permit Number |
15070056 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-29 17:32:52 | ****CORRECTIONS**** | | | | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. REVISE PLAN TO INCLUDE GOVERNING CODE. CODE | | | REFERENCED IS NOT GOVERNING CODE DUE TO APPLICATION | | | DATE, FS553. | | | | | | 2. REVISE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. | | | | | | 3. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | | HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND | | | OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 704.1. THE | | | CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION | | | NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | | HEIGHT: | | | | | | STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS | | | - AWNING, CASEMENT, SINGLE HUNG? | | | | | | STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE. | | | CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE | | | WINDOW IS FULLY OPEN. | | | | | | STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE. | | | THIS CAN BE OBTAINED FROM THE MANUFACTURER. | | | | | | 4. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | | FAC9N-3, FBC 5TH EDITION 301. | | | | | | FOR FLORIDA STATE PRODUCT APPROVAL, PROVIDE THE | | | FOLLOWING FOR EACH PRODUCT: | | | | | | COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE | | | THE CODE VERSION, PRODUCT APPROVAL NUMBER, STATUS, | | | GENERAL INFORMATION ABOUT THE PRODUCT) | | | EVALUATION REPORT | | | INSTALLATION INSTRUCTIONS | | | | | | |
|