| Plan Review Notes For Permit 15070042 |
| Permit Number |
15070042 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-08-18 12:32:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THERE ARE MULTIPLE REFERENCES TO FBC 2010; REVISE TO | | | GOVERNING CODE (FBC 2014). | | | | | | 2ND REVIEW, SEE STRUCTURAL NOTES AND ANY OTHER PLACES | | | AS APPLICABLE; REVISE TO GOVERNING CODE. | | | | | | 2. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 2014 | | | RESIDENTIAL 301. | | | | | | NOT ADDRESSED. INCLUDE WIND SPEED AND EXPOSURE | | | CLASSIFICATION. | | | | | | 3. STANDARDS REFERENCED STATE "CURRENT EDITION"; SEE | | | FBC 2014 RESIDENTIAL CHAPTER 46. STANDARDS TO COMPLY | | | WITH THE GOVERNING CODE. IF ENGINEER WOULD LIKE TO | | | PROPOSE A DIFFERENT EDITION, THIS IS TO BE SUBMITTED | | | USING ALTERNATIVE MATERIALS AND METHODS FBC 104.11. | | | | | | NOT ADDRESSED. | | | | | | 4. PLAN STATES THAT BUILDING TYPE IS IIB, CONFIRM AND | | | CLARIFY OR REVISE. TYPE IIB IS NON COMBUSTIBLE. MOST | | | SFD STRUCTURES HAVE WOOD TRUSSES OR FRAMING, FBC 107. | | | | | | NOT ADDRESSED. | | | | | | NEW COMMENT: | | | | | | 5. PLAN SHOWS EXISTING IMPACT WINDOWS. PROVIDE PERMIT | | | NUMBER FOR THIS WORK. IT IS NOT CONSIDERED "EXISTING" | | | IF NOT PERMITTED. | | | | | | 6. WHEN RESUBMITTING, CONTRACTOR COMPANY NAME SHOULD BE | | | IN THE LINE FOR "CONTRACTOR." AS THIS IS HOW PLANS ARE | | | FILED IN THIS DEPARTMENT, ANY OTHER INFORMATION | | | (QUALIFIER OR CONTACT PERSON) IN THIS LINE COULD CAUSE | | | THE PLAN TO BE MISPLACED / MISFILED. | | | | | | | | | | | | | | | | | | |
|