| Plan Review Notes For Permit 15070042 |
| Permit Number |
15070042 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-07 15:35:31 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THERE ARE MULTIPLE REFERENCES TO FBC 2010; REVISE TO | | | GOVERNING CODE (FBC 2014). | | | | | | 2. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 2014 | | | RESIDENTIAL 301. | | | | | | 3. STANDARDS REFERENCED STATE "CURRENT EDITION"; SEE | | | FBC 2014 RESIDENTIAL CHAPTER 46. STANDARDS TO COMPLY | | | WITH THE GOVERNING CODE. IF ENGINEER WOULD LIKE TO | | | PROPOSE A DIFFERENT EDITION, THIS IS TO BE SUBMITTED | | | USING ALTERNATIVE MATERIALS AND METHODS FBC 104.11. | | | | | | 4. PLAN STATES THAT BUILDING TYPE IS IIB, CONFIRM AND | | | CLARIFY OR REVISE. TYPE IIB IS NON COMBUSTIBLE. MOST | | | SFD STRUCTURES HAVE WOOD TRUSSES OR FRAMING, FBC 107. | | | | | | | | | |
|