2015-08-10 09:50:242ND REVIEW: FBC 2014 MECHANICAL
  
 1) BALANCED RETURN AIR REQUIRED IN ACCORDANCE WITH
 SECTION M1602.4 FBC-14 RESIDENTIAL. SHOW HOW AIR IS
 BEING RETURNED FROM THE BEDROOMS TO THE AIR HANDLER IN
 THE NEW CLOSET.
 2) PROVIDE A SUB-PERMIT AND DRAWINGS FOR INSTALLATION
 OF THE NEW AIR HANDLER CLOSET, OR INDICATE THAT IT WILL
 BE DONE UNDER A SEPARATE PERMIT.
  