| 2015-07-01 15:45:56 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | |
| | 1) THE PREVIOUSLY UNCONDITIONED HOUSE NOW BEING |
| | CONDITIONED WITH A NEW AC SYSTEM IS REQUIRED TO TO BE |
| | BROUGHT INTO FULL COMPLIANCE WITH THE FLORIDA ENERGY |
| | CONSERVATION CODE 2014 PER SECTION R101.4.6. SUBMIT TWO |
| | COPIES OF EITHER PRESCRIPTIVE FORM R402, OR THE |
| | PERFORMANCE BASED FORM R405, OR A FLORIDA RESCHECK |
| | COMPUTER PRINTOUT- REFERENCE SECTION R101.5.1.1. PLEASE |
| | SUBMIT A PLAN THAT CORRELATES WITH THE CHOSEN |
| | COMPLIANCE FORM, THAT INDICATES INSULATION R-VALUES FOR |
| | WALLS, AND ATTICS, AND EFFICIENCY RATINGS FOR WINDOWS |
| | AND DOORS. PLEASE NOTE THAT ALL ENVELOPE COMPONENTS NOT |
| | MEETING COMPLIANCE SHALL BE BROUGHT UP TO THE CURRENT |
| | STANDARDS REQUIRED PER THE COMPLIANCE PATH CHOSEN. |
| | 2) THE SUBMITTED AC LOAD CALCULATION FORM IS NOT AN |
| | APPROVED ACCA MANUAL J METHOD. PLEASE PROVIDE A |
| | CALCULATION USING APPROVED ACCA MANUAL J SOFTWARE AND |
| | INCLUDE THE ROOM-BY-ROOM WORKSHEETS- SEE SECTION |
| | R403.6.1 FBC-14 ENERGY CONSERVATION. |
| | 3) SHOW THE REQUIRED MINIMUM CLEARANCES FOR THE NEW AIR |
| | HANDLER IN THE CLOSET PER SECTION M1305.1.1 FBC-14 |
| | RESIDENTIAL- 3" ALONG THE BACK, SIDES, AND TOP, WITH |
| | THE TOTAL WIDTH OF THE ENCLOSING SPACE AT LEAST 12" |
| | WIDER THAN THE AIR HANDLER. |
| | 4) THE SUBMITTED PLAN DOES NOT INDICATE A RETURN AIR |
| | SYSTEM- REFERENCE SECTION M1602.4 AND REVISE THE PLAN |
| | ACCORDINGLY. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |