2015-07-01 15:45:561ST REVIEW: FBC 2014 MECHANICAL
  
 1) THE PREVIOUSLY UNCONDITIONED HOUSE NOW BEING
 CONDITIONED WITH A NEW AC SYSTEM IS REQUIRED TO TO BE
 BROUGHT INTO FULL COMPLIANCE WITH THE FLORIDA ENERGY
 CONSERVATION CODE 2014 PER SECTION R101.4.6. SUBMIT TWO
 COPIES OF EITHER PRESCRIPTIVE FORM R402, OR THE
 PERFORMANCE BASED FORM R405, OR A FLORIDA RESCHECK
 COMPUTER PRINTOUT- REFERENCE SECTION R101.5.1.1. PLEASE
 SUBMIT A PLAN THAT CORRELATES WITH THE CHOSEN
 COMPLIANCE FORM, THAT INDICATES INSULATION R-VALUES FOR
 WALLS, AND ATTICS, AND EFFICIENCY RATINGS FOR WINDOWS
 AND DOORS. PLEASE NOTE THAT ALL ENVELOPE COMPONENTS NOT
 MEETING COMPLIANCE SHALL BE BROUGHT UP TO THE CURRENT
 STANDARDS REQUIRED PER THE COMPLIANCE PATH CHOSEN.
 2) THE SUBMITTED AC LOAD CALCULATION FORM IS NOT AN
 APPROVED ACCA MANUAL J METHOD. PLEASE PROVIDE A
 CALCULATION USING APPROVED ACCA MANUAL J SOFTWARE AND
 INCLUDE THE ROOM-BY-ROOM WORKSHEETS- SEE SECTION
 R403.6.1 FBC-14 ENERGY CONSERVATION.
 3) SHOW THE REQUIRED MINIMUM CLEARANCES FOR THE NEW AIR
 HANDLER IN THE CLOSET PER SECTION M1305.1.1 FBC-14
 RESIDENTIAL- 3" ALONG THE BACK, SIDES, AND TOP, WITH
 THE TOTAL WIDTH OF THE ENCLOSING SPACE AT LEAST 12"
 WIDER THAN THE AIR HANDLER.
 4) THE SUBMITTED PLAN DOES NOT INDICATE A RETURN AIR
 SYSTEM- REFERENCE SECTION M1602.4 AND REVISE THE PLAN
 ACCORDINGLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER