Plan Review Notes
Plan Review Notes For Permit 15070020
Permit Number 15070020
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-07-31 12:32:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PROVIDE BUILDING FLOOR PLAN, INCLUDING OCCUPANY
 LOADS AND ALL EXITS, EXIT SIGNS, EMERGENCY LIGHTS, ETC.
  
 2. DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY,
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS SIDE.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  