2015-09-15 13:38:37BUILDING PLAN REVIEW
 *******************************
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
  
 REVIEW OF ALTERNATIVE PRODUCT APPROVAL (NOA #
 14-0506.07) SUBMITTED BY THE CONTRACTOR FOR THE
 PROPOSED ARTEMANOS HAND MADE CLAY TILE SET IN MORTAR.
  
 USING THE ZONE 3 WIND PRESSURE FROM THE PROVIDED
 ENGINEER'S CALCULATION, THE ATTACHMENT RESISTANCE
 CALCULATION NOW LOOKS AS FOLLOWS:
  
 MAXIMUM ZONE 3 WIND PRESSURE, P3 = -130 PSF (SUBMITTED
 ENGINEER'S CALCULATION)
  
 ARTEMANOS HAND MADE CLAY TILE TO BE INSTALLED PER NOA #
 14-0506.07
  
 AERODYNAMIC MULTIPLIER, A = 0.329 FT3 (TABLE 2, PAGE 3
 OF 5)
  
 RESTORING MOMENT DUE TO GRAVITY, MG = 4.85 FT-LBF
 (SLOPE 4/12, TABLE 3, PAGE 3 OF 5)
  
 UPLIFT MOMENT, MR = (P3 X A) - MG = (130 X 0.329) -
 4.85 = 37.92 FT-LBF (REQUIRED)
  
 COMPARED TO ATTACHMENT RESISTANCE PROVIDED BY MORTAR
 SET ARTEMANOS TILE PER TABLE 7, PAGE 4 OF 5:
  
 PROVIDED ATTACHMENT RESISTANCE, MF = 71.85 FT-LBF >
 37.92 FT-LBF REQUIRED
  
 THEREFORE ARTEMANOS HAND MADE CLAY TILE SET IN MORTAR
 INSTALLED PER NOA # 14-0506.07, IS OK
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]