| Plan Review Notes For Permit 15070016 |
| Permit Number |
15070016 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-06 17:56:58 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | | CODE: FBC- 5TH EDITION(2014)-RESIDENTIAL. | | | | | | NOTE: AFTER HAVING A CHANCE OF A SECOND REVIEW OF THE | | | CLAY TILE NOA I REALIZED | | | THAT THE PROPOSED MORTAR INSTALLATION IS NOT ALLOWED. | | | SEE COMMENTS BELOW | | | REGARDING THE NOA LIMITATIONS: | | | | | | 1- ACCORDING TO ROOF TILE NOA 13-0923.06 SUBMITTED | | | NAIL-ON SYSTEMS AND MORTAR SET SYSTEMS IS FOR SANTA ANA | | | MISSION TILE - TOLEDO, CASTILLA, AND MARBELLA ROOF | | | TILES ONLY. NOT FOR ANTIGUA CAP. THE ONLY OPTION FOR | | | ANTIGUA CAP IS 3M 2-COMPONENT FOAM ROOF TILE ADHESIVE | | | AH-160 (SEE TABLE 5(B) AND TABLE 5(C) ON NOA | | | SUBMITTED). | | | | | | PROVIDE PRODUCT APPROVAL FOR ROOF TILE ADHESIVE AH-160 | | | AS REQUIRED BY DCA RULE 9N-3. | | | | | | AS AN ALTERNATIVE, CONTRACTOR MAY APPLY FOR SITE | | | SPECIFIC INSTALLATION TO BE APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | |
|