Plan Review Notes
Plan Review Notes For Permit 15070016
Permit Number 15070016
Review Stop B
Sequence Number 2
Notes
Date Text
2015-07-06 17:56:58RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: FBC- 5TH EDITION(2014)-RESIDENTIAL.
  
 NOTE: AFTER HAVING A CHANCE OF A SECOND REVIEW OF THE
 CLAY TILE NOA I REALIZED
 THAT THE PROPOSED MORTAR INSTALLATION IS NOT ALLOWED.
 SEE COMMENTS BELOW
 REGARDING THE NOA LIMITATIONS:
  
 1- ACCORDING TO ROOF TILE NOA 13-0923.06 SUBMITTED
 NAIL-ON SYSTEMS AND MORTAR SET SYSTEMS IS FOR SANTA ANA
 MISSION TILE - TOLEDO, CASTILLA, AND MARBELLA ROOF
 TILES ONLY. NOT FOR ANTIGUA CAP. THE ONLY OPTION FOR
 ANTIGUA CAP IS 3M 2-COMPONENT FOAM ROOF TILE ADHESIVE
 AH-160 (SEE TABLE 5(B) AND TABLE 5(C) ON NOA
 SUBMITTED).
  
 PROVIDE PRODUCT APPROVAL FOR ROOF TILE ADHESIVE AH-160
 AS REQUIRED BY DCA RULE 9N-3.
  
 AS AN ALTERNATIVE, CONTRACTOR MAY APPLY FOR SITE
 SPECIFIC INSTALLATION TO BE APPROVED BY THE BUILDING
 OFFICIAL.
  