2015-07-01 18:15:07RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: FBC- 5TH EDITION(2014)-RESIDENTIAL.
  
 1- ENGINEER TO REVISE THE SITE SPECIFIC ENGINEERING
 SUBMITTED :
 A) THIS IS NOT ONE STORY HIGH ROOF. THIS IS A TWO STORY
 HOUSE. REVISE MEAN ROOF HEIGHT AND DESIGN PRESSURES AS
 REQUIRED. SEC. R301 OF FBC-5TH EDITION-RESIDENTIAL.
  
 B) THE BUILDING DEPARTMENT IS INCORRECT. THIS IS CITY
 OF WEST PALM BEACH NO TOWN OF PALM BEACH. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 ****NOTE: ADDITIONAL COMMENT:
  
 C) ROOF TILE SPECIFIED BY THE ENGINEER DOESN'T MATCH
 ROOF TILE SPECIFIED BY THE CONTRACTOR ON THE PERMIT
 APPLICATION. CONTRACTOR SPECIFIED "SANTA ANA MISSION
 ANTIGUA TILE". REVISE AS REQUIRED AND REVISE THE
 CALCULATIONS USING THE CORRECT AERODYNAMIC MULTIPLIER
 AND RESTORING MOMENT. SEC. R301.
  