| Date |
Text |
| 2015-07-08 08:46:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET A-4 IS MISSED LABELED AS SECOND FLOOR. |
| | |
| | 2) SHEET A-8 INDICATES INCORRECT CODE REFERENCES. THE |
| | PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH |
| | EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING THE |
| | 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | 3) THE BUILDING IS REQUIRED TO HAVE A MONOTORED FIRE |
| | SPRINKLER SYSTEM PER NFPA 101, CHAPTER 12, NEW ASSEMBLY |
| | OCCUPANCIES, 12.3.5. CONCEPTUAL DRAWING SHALL BE |
| | SUBMIITED WITH THIS PERMIT AND SHOP DRAWINGS SHALL |
| | FOLLOW. |
| | |
| | 4) THE BUILDING IS REQUIRED TO HAVE A COMPLETE FIRE |
| | ALARM SYSTEM PER NFPA 101, CHAPTER 12, NEW ASSEMBLY |
| | OCCUPANCIES, 12.3.4. CONCEPTUAL DRAWING SHALL BE |
| | SUBMIITED WITH THIS PERMIT AND SHOP DRAWINGS SHALL |
| | FOLLOW. |
| | |
| | 5) SHEET A-3 & A-9 SHOW 2 EXIT ACCESS DOORS THAT ARE |
| | TOO CLOSE TO EACH OTHER. EXITS SHALL BE REMOTELY |
| | LOCATED FROM EACH OTHER PER NFPA 101, CHAPTER 7 MEANS |
| | OF EGRESS, 7.4. |
| | |
| | 6) IS THE STAIR NEW OF EXISTING? THERE IS NO STAIR |
| | DETAIL. PROVIDE ALL DETAIL PER CHAPTER 7 , 7.2.2.. |
| | INCLUDING ACCESSIBILITY AND AREA OF REFUGE. THE STAIR |
| | SHALL LEAD TO A PUBLIC WAY; UNABLE TO DETERMINE THE |
| | PUBLIC WAY. UNABLE TO DETERMINE STAIRS DIMENSIONS, |
| | CONSTRUCTION MATERIAL. |
| | |
| | 7) PROVIDE THE TOTAL EXIT TRAVEL DISTANCE FROM THE 3RD |
| | FLOOR ALONG THE UNPROTECTED OUTSIDE STAIR TO THE BOTTOM |
| | TREAD, MEETING THE REQUIREMENTS PER CHAPTER 12, 12.2.6 |
| | |
| | 8) THERE IS NO LIGHTING ON THE EXIT STAIR. |
| | |
| | 9) IS THE STAIR APPROVED TO BE IN THE ALLEY? |
| | |
| | 10) PROVIDE EXIT STAIR SEPARATION PER CHAPTER 7, |
| | 7.2.2.6.3 |
| | |
| | 11) PROTECTION OF OPENINGS UNDER THE STAIR SHALL MEET |
| | CHAPTER 7, 7.2.2.6.4 |
| | |
| | 12) THE ELEVATOR SHALL COMPLY WITH NFPA 1, CHAPTER 11, |
| | BUILDING SERVICES,11.3 |
| | |
| | 13) SHEET A-8 SHOWS TWO EXIT ACCESSES PASSING THROUGH A |
| | "PREP/KITCHEN". PER CHAPTER 7, 7.5.2 EXITS SHALL NOT |
| | PASS THROUGH KITCHENS. |
| | |
| | 14) SHEET A-10 SHOWS THE WORDS "FIRE SHUTTER" OVER A |
| | WINDOW OPENINGS. PLEASE EXPLAIN THE FUNCTION AND |
| | PURPOSE OF THESE. |
| | |
| | 15) FURTHER COMMENT MAY BE PROVIDED ON THE SUBMIITAL |
| | AND REVIEW OF THE ABOVE. |
| | |
| | |
| | |