| 2015-07-14 06:44:50 | 1) THE PLANS SHOW A STORAGE AREA. INDICATE ON THE PLANS |
| | WHAT TYPE OF ITEMS WILL BE STORED IN THIS AREA. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 2) SHT. A-2 - THE BUILDING SQ. FT. SUMMARY TABLE FOR |
| | BUILDING "B" SHOWS A "TEACHER PLANNING AREA." THIS AREA |
| | IS NOT IDENTIFIED ON THE PLANS. CLARIFY. |
| | 3) SHT. A-2 - BUILDING SQUARE FOOT SUMMARY TABLE - |
| | LISTS AN "UNASSIGNED" AREA. PLEASE CLARIFY AS TO WHAT |
| | THIS SPACE IS AND WHERE IT IS. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 4) THE PERMIT APPLICATION IS ONLY FOR BUILDING "B". WHY |
| | HAS INFORMATION FOR BUILDING "A" BEEN SUBMITTED? |
| | CLARIFY. |
| | 5) A SERVICE SINK IS REQUIRED PER THE 2014 |
| | FBC-PLUMBING, TABLE 403.1. |
| | 6) SUBMIT A SANITARY AND WATER RISER FOR ANY CHANGES |
| | BEING MADE TO THE PLUMBING SYSTEM. WPB AMEND. TO FBC |
| | SEC.107.3.5.1.3. SUBMIT A NARRATIVE THAT CLEARLY |
| | EXPLAINS THE SCOPE OF WORK TO BE DONE IN THIS |
| | BUILDING.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 7) SHOW THE LOCATION OF THE WATER HEATER IN THE |
| | BUILDING. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 8) THE LEADING EDGE OF THE HIGH DRINKING FOUNTAIN MAY |
| | HAVE IT'S LEADING EDGE MORE THAN 27 INCHES ABOVE THE |
| | FINISH FLOOR WHICH WOULD ONLY ALLOW IT PROTRUDE INTO |
| | THE CIRCULATION PATH A MAXIMUM OF 4 INCHES PER THE 2010 |
| | FBC-ACCESSIBILITY, SEC.307.2. A SKIRT MAY HAVE TO BE |
| | ADDED TO THE BOTTOM OF THE DRINKING FOUNTAIN TO BRING |
| | THE LEADING EDGE BELOW 27 INCHES. |
| | |
| | PLUMBING PLAN REVIEW |