Plan Review Notes
Plan Review Notes For Permit 15061473
Permit Number 15061473
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-14 06:44:501) THE PLANS SHOW A STORAGE AREA. INDICATE ON THE PLANS
 WHAT TYPE OF ITEMS WILL BE STORED IN THIS AREA. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) SHT. A-2 - THE BUILDING SQ. FT. SUMMARY TABLE FOR
 BUILDING "B" SHOWS A "TEACHER PLANNING AREA." THIS AREA
 IS NOT IDENTIFIED ON THE PLANS. CLARIFY.
 3) SHT. A-2 - BUILDING SQUARE FOOT SUMMARY TABLE -
 LISTS AN "UNASSIGNED" AREA. PLEASE CLARIFY AS TO WHAT
 THIS SPACE IS AND WHERE IT IS. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) THE PERMIT APPLICATION IS ONLY FOR BUILDING "B". WHY
 HAS INFORMATION FOR BUILDING "A" BEEN SUBMITTED?
 CLARIFY.
 5) A SERVICE SINK IS REQUIRED PER THE 2014
 FBC-PLUMBING, TABLE 403.1.
 6) SUBMIT A SANITARY AND WATER RISER FOR ANY CHANGES
 BEING MADE TO THE PLUMBING SYSTEM. WPB AMEND. TO FBC
 SEC.107.3.5.1.3. SUBMIT A NARRATIVE THAT CLEARLY
 EXPLAINS THE SCOPE OF WORK TO BE DONE IN THIS
 BUILDING.WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHOW THE LOCATION OF THE WATER HEATER IN THE
 BUILDING. WPB AMEND. TO FBC SEC. 107.2.1.
 8) THE LEADING EDGE OF THE HIGH DRINKING FOUNTAIN MAY
 HAVE IT'S LEADING EDGE MORE THAN 27 INCHES ABOVE THE
 FINISH FLOOR WHICH WOULD ONLY ALLOW IT PROTRUDE INTO
 THE CIRCULATION PATH A MAXIMUM OF 4 INCHES PER THE 2010
 FBC-ACCESSIBILITY, SEC.307.2. A SKIRT MAY HAVE TO BE
 ADDED TO THE BOTTOM OF THE DRINKING FOUNTAIN TO BRING
 THE LEADING EDGE BELOW 27 INCHES.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  