2015-07-08 17:42:401ST REVIEW: FBC 2014 MECHANICAL
  
 1) SHEET A3: SHOW THE SUPPLY DUCT SIZE AND DUCT RUN TO
 THE RELOCATED DIFFUSER IN CLASSROOM #5. INDICATE THE
 CFM SUPPLY AMOUNT AT THE DIFFUSER.
 2) PROVIDE CALCULATIONS VERIFYING COMPLIANCE WITH
 SECTION 809.2 FBC-14 EXISTING BUILDING- ALTERED
 EXISTING SYSTEMS: MECHANICAL VENTILATION SYSTEMS THAT
 ARE ALTERED, RECONFIGURED, OR EXTENDED SHALL PROVIDE
 NOT LESS THAN 5 CUBIC FEET PER MINUTE PER PERSON OF
 OUTDOOR AIR AND NOT LESS THAN 15 CFM OF VENTILATION AIR
 PER PERSON; OR NOT LESS THAN THE AMOUNT OF VENTILATION
 AIR DETERMINED BY THE INDOOR QUALITY PROCEDURE OF
 ASHRAE 62.1- 2010.
  