| Plan Review Notes For Permit 15061473 |
| Permit Number |
15061473 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-08 17:42:40 | 1ST REVIEW: FBC 2014 MECHANICAL | | | | | | 1) SHEET A3: SHOW THE SUPPLY DUCT SIZE AND DUCT RUN TO | | | THE RELOCATED DIFFUSER IN CLASSROOM #5. INDICATE THE | | | CFM SUPPLY AMOUNT AT THE DIFFUSER. | | | 2) PROVIDE CALCULATIONS VERIFYING COMPLIANCE WITH | | | SECTION 809.2 FBC-14 EXISTING BUILDING- ALTERED | | | EXISTING SYSTEMS: MECHANICAL VENTILATION SYSTEMS THAT | | | ARE ALTERED, RECONFIGURED, OR EXTENDED SHALL PROVIDE | | | NOT LESS THAN 5 CUBIC FEET PER MINUTE PER PERSON OF | | | OUTDOOR AIR AND NOT LESS THAN 15 CFM OF VENTILATION AIR | | | PER PERSON; OR NOT LESS THAN THE AMOUNT OF VENTILATION | | | AIR DETERMINED BY THE INDOOR QUALITY PROCEDURE OF | | | ASHRAE 62.1- 2010. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|