Plan Review Notes
Plan Review Notes For Permit 15061473
Permit Number 15061473
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-23 12:20:23PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. NEC 220.16 (B) OTHER THAN DWELLING UNITS. LOADS FOR
 NEW CIRCUITS OR EXTENDED CIRCUITS IN OTHER THAN
 DWELLING UNITS SHALL BE CALCULATED IN ACCORDANCE WITH
 EITHER 220.12 OR 220.14, AS APPLICABLE.
 2. NEC 230.70(B) MARKING. EACH SERVICE DISCONNECT SHALL
 BE PERMANENTLY MARKED TO IDENTIFY IT AS A SERVICE
 DISCONNECT.
 3. NEC 408.4 EVERY CIRCUIT AND CIRCUIT MODIFICATION
 SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT,
 AND SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
 4. PER FBC EMERGENCY LIGHTING IS REQUIRED.
 5. COMPLIANCE WITH FBC-ENERGY SECTION 505 IS REQUIRED.
 6. PROVIDE A DETAIL OF THE ATTACHMENT FOR THE NEW
 LUMINARIES AS PER THE REQUIREMENTS OF NEC 410.PART IV
 7. SEPARATE FIRE ALARM DRAWINGS AND PERMITS ARE
 REQUIRED.
 8. MANUAL FIRE ALARM PULL BOX REQUIRED WITHIN 5' OF
 EVERY EXIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  