| 2015-07-23 12:20:23 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. NEC 220.16 (B) OTHER THAN DWELLING UNITS. LOADS FOR |
| | NEW CIRCUITS OR EXTENDED CIRCUITS IN OTHER THAN |
| | DWELLING UNITS SHALL BE CALCULATED IN ACCORDANCE WITH |
| | EITHER 220.12 OR 220.14, AS APPLICABLE. |
| | 2. NEC 230.70(B) MARKING. EACH SERVICE DISCONNECT SHALL |
| | BE PERMANENTLY MARKED TO IDENTIFY IT AS A SERVICE |
| | DISCONNECT. |
| | 3. NEC 408.4 EVERY CIRCUIT AND CIRCUIT MODIFICATION |
| | SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, |
| | AND SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL |
| | INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS. |
| | 4. PER FBC EMERGENCY LIGHTING IS REQUIRED. |
| | 5. COMPLIANCE WITH FBC-ENERGY SECTION 505 IS REQUIRED. |
| | 6. PROVIDE A DETAIL OF THE ATTACHMENT FOR THE NEW |
| | LUMINARIES AS PER THE REQUIREMENTS OF NEC 410.PART IV |
| | 7. SEPARATE FIRE ALARM DRAWINGS AND PERMITS ARE |
| | REQUIRED. |
| | 8. MANUAL FIRE ALARM PULL BOX REQUIRED WITHIN 5' OF |
| | EVERY EXIT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |