| 2015-07-10 13:27:50 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15061473 |
| | ADD: 2401 MERCER AVE. BLDG. B |
| | CONT: GREENVIEW CONSTRUCTION/ CHRISTOPHER TYSON |
| | TEL: (561)727-5013 |
| | E-MAIL: [email protected] |
| | |
| | 5TH EDITION OF THE FLORIDA BUILDING CODE (2014) |
| | 5TH EDITION OF THE EXISTING BUILDING CODE (2014) |
| | |
| | 5TH EDITION OF THE EXISTING BUILDING CODE LEVEL II |
| | 801.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JULY 10/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-2 : |
| | |
| | 1A) THE PLANS INDICATE THEY WERE DESIGNED TO THE 2010 |
| | FBC. AS OF JUNE 30/ 2015 THE 5TH EDITION OF THE FLORIDA |
| | BUILDING CODE (2014) WAS ADOPTED STATE WIDE. |
| | |
| | 1B) THIS SHEET ALSO INDICATES THIS IS A LEVEL II |
| | ALTERATION. BUILDING A, THIS IS CONSIDERED A "CHANGE OF |
| | OCCUPANCY", IN 2005-2008 ART STUDIO, THEN IN 2008-2009 |
| | IT WAS A RETAIL STORE AND IN2011-2012 A BUSINESS |
| | OCCUPANCY AS A CONTRACTING OFFICE. THE BUILDING WILL |
| | NEED TO COMPLY WITH THE 5TH EDITION FBC-EXISTING |
| | BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. NOTE IN THE |
| | EXISTING BUILDING CODE CHAPTERS HAVE BEEN MOVED. |
| | |
| | 1C) UNDER THE 5TH EDITION OF THE FBC- EXISITNG BUILDING |
| | CODE 301.1 ALL EXISITNG BUILDINGS SHALL COMPLY WITH ONE |
| | OF THE METHODSLISTED IN SECTION 301.1.1 THROUGH 301.1.3 |
| | AS SELECTED BY THE APPLICANT. |
| | |
| | 2) SHEET A-2 INDICATES A STORAGE OCUPANCY BUT THE TYPE |
| | OF STORAGE IS NOT DECLARED S1 OR S2? MAY REQUIRE A 2 HR |
| | OCCUPANCY SEPARATION WALL. 2014 FBC-B TABLE 508.4. |
| | |
| | 3) SHEET A-2 INDICATES A NEW RATED WALL BETWEEN THE |
| | STORAGE OCCUPANCY & EDUCATIONAL OCCUPANCY, PLEASE |
| | PROVIDE A RATED WALL ASSEMBLY TYPE. 2010 FBC-B 707.5 |
| | CONTINUITY. |
| | |
| | 4) SHEET A-2 THE EXIT ACCESS CORRIDOR BETWEEN |
| | CLASSROOMS 4 & 6 IS 5 FEET WIDE. PLEASE REVIEW TABLE |
| | 1018.2 (2014) FBC-B. |
| | |
| | 5) SHEET A-2 CLASSROOM 2 & 4 BOTH HAVE ROLLED DOWN THE |
| | PART OF A OCCUPANT. WHEN THERE IS A PART OF AN OCCUPANT |
| | IN FIGURING THE OCCUPANT LOAD FOR A ROOM, YOU ALWAYS |
| | ROUND UP TO THE NEXT WHOLE NUMBER. 2014 FBC-B 1004.1.1. |
| | |
| | 6) SHEET A-2 SHOWS IN CLASSROOM # 4 A NEW EGRESS |
| | WINDOW. PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE NEW |
| | WINDOW. SHOW COMPLIANCE WITH: |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(B) WINDOWS |
| | |
| | 7) 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 8) PLEASE SHOW COMPLIANCE WITH: |
| | 8A) 2014 FBC-B 468.3.2. GLARE FROM NATURAL LIGHT. |
| | |
| | 8B) 2014 FBC-B 468.3.7.5 GLARE ELIMINATION. |
| | |
| | 8C) 2014 FBC-B 468.3.5.5 WALLS |
| | |
| | 8D) 2014 FBC-B 468.3.7.4 ILLUMINATION FAILURE OF |
| | GENERAL AND MEANS OF EGRESS LUMINARIS. |
| | |
| | 8E) 2014 FBC-B 468.2.3 OUTDOOR WASTE CONTAINERS. |
| | |
| | 9) THE STORAGE ROOM MAY NEED TO COMPLY WITH 2014 FBC-B |
| | 468.3.6.5. CHEMICAL STORAGE. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |