| 2015-07-16 10:37:12 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | 7/16/15 |
| | |
| | 1) THE SUBMITTED ENERGY GAUGE FORM 506-2010 IS |
| | OUTDATED. THE FBC-2014 FIFTH EDITION OF THE ENERGY |
| | CONSERVATION CODE WENT INTO EFFECT ON JUNE 30, 2015, ON |
| | THE DAY OF THIS PERMIT APPLICATION. PLEASE SEE SECTION |
| | C101.5 FOR ACCEPTABLE COMPLIANCE FORMS. |
| | 2) REVISE THE AC PLAN ON SHEET 3.1 TO SHOW THE 4 ZONES |
| | AS INDICATED IN THE SUBMITTED WRIGHTSOFT AC LOAD |
| | CALCULATIONS. |
| | 3) PLEASE ADJUST THE AC CALCULATIONS TO SHOW THE |
| | CORRECT DESIGN TEMPERATURES PER THE ASHRAE FUNDAMENTALS |
| | HANDBOOK: WPB SUMMER DRY BULB- 91, WET BULB- 78. |
| | 4) ADJUST THE AC CALCULATIONS TO INDICATE INTERNAL HEAT |
| | GAIN LOADS. |
| | 5) PLEASE REVIEW SECTION 809.1 FBC-14 EXISTING |
| | BUILDING, AND PROVIDE A MINIMUM VENTILATION RATE |
| | CALCULATION ON THE PLAN FOR THE RECONFIGURED ROOMS AND |
| | SPACES- REFERENCE TABLE 403.3 FBC-14 MECHANICAL. PLEASE |
| | NOTE THE CURRENT PLAN IS NOT INDICATING A MEANS OF O/A |
| | SUPPLY: PLEASE CORRECT. |
| | 6) SHEET 3.1: PLACE THE MODEL NUMBERS OF THE INDOOR |
| | UNITS AT THEIR CORRESPONDING LOCATIONS ON THE PLAN. |
| | 7) SHEET 3.1: THE NEW CU SHALL BE ANCHORED TO RESIST |
| | WIND LOADS PER SECTION 301.15 FBC-10 MECH. REFER TO |
| | SECTION 1609 FBC-10 BUILDING AND STRUCTURAL DETAILS FOR |
| | THE PAD, AND TIE DOWN OF THE UNIT. |
| | 8) SHEET 3.1: PROVIDE CONDENSATE DISPOSAL DETAILS FOR |
| | THE INDOOR UNITS. SHOW THE TYPE AND SIZE OF PIPE, PIPE |
| | RUNS, AND DISCHARGE LOCATIONS- SEE SECTION 307. |
| | |