Plan Review Notes
Plan Review Notes For Permit 15061471
Permit Number 15061471
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-16 10:37:121ST REVIEW: FBC 2014 MECHANICAL
 7/16/15
  
 1) THE SUBMITTED ENERGY GAUGE FORM 506-2010 IS
 OUTDATED. THE FBC-2014 FIFTH EDITION OF THE ENERGY
 CONSERVATION CODE WENT INTO EFFECT ON JUNE 30, 2015, ON
 THE DAY OF THIS PERMIT APPLICATION. PLEASE SEE SECTION
 C101.5 FOR ACCEPTABLE COMPLIANCE FORMS.
 2) REVISE THE AC PLAN ON SHEET 3.1 TO SHOW THE 4 ZONES
 AS INDICATED IN THE SUBMITTED WRIGHTSOFT AC LOAD
 CALCULATIONS.
 3) PLEASE ADJUST THE AC CALCULATIONS TO SHOW THE
 CORRECT DESIGN TEMPERATURES PER THE ASHRAE FUNDAMENTALS
 HANDBOOK: WPB SUMMER DRY BULB- 91, WET BULB- 78.
 4) ADJUST THE AC CALCULATIONS TO INDICATE INTERNAL HEAT
 GAIN LOADS.
 5) PLEASE REVIEW SECTION 809.1 FBC-14 EXISTING
 BUILDING, AND PROVIDE A MINIMUM VENTILATION RATE
 CALCULATION ON THE PLAN FOR THE RECONFIGURED ROOMS AND
 SPACES- REFERENCE TABLE 403.3 FBC-14 MECHANICAL. PLEASE
 NOTE THE CURRENT PLAN IS NOT INDICATING A MEANS OF O/A
 SUPPLY: PLEASE CORRECT.
 6) SHEET 3.1: PLACE THE MODEL NUMBERS OF THE INDOOR
 UNITS AT THEIR CORRESPONDING LOCATIONS ON THE PLAN.
 7) SHEET 3.1: THE NEW CU SHALL BE ANCHORED TO RESIST
 WIND LOADS PER SECTION 301.15 FBC-10 MECH. REFER TO
 SECTION 1609 FBC-10 BUILDING AND STRUCTURAL DETAILS FOR
 THE PAD, AND TIE DOWN OF THE UNIT.
 8) SHEET 3.1: PROVIDE CONDENSATE DISPOSAL DETAILS FOR
 THE INDOOR UNITS. SHOW THE TYPE AND SIZE OF PIPE, PIPE
 RUNS, AND DISCHARGE LOCATIONS- SEE SECTION 307.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  