| | PROJECT: OFFICE RENNOVATION |
| | PERMIT#: 15061471 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) PROVIDE A PANEL SCHEDULE AND INDICATE THE OCPD AND |
| | WIRE SIZES. EVERY CIRCUIT AND CIRCUIT MODIFICATION |
| | SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, |
| | AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | |
| | 2) INDICATE THE REQUIRED A/C DISCONNECTS FOR NEW |
| | MECHANICAL EQUIPMENT. NEC 440.14 INCLUDE THE CIRCUIT |
| | AND DISCONNECT REQUIRED FOR THE DUCTLESS WALL MOUNT |
| | INDOOR UNIT |
| | |
| | 3) PROVIDE A GFI RECEPTACLE OUTLET AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, AIR |
| | CONDITIONING, AND REFRIGERATION EQUIPMENT. 210.63 |
| | |
| | 4) INDICATE GFI PROTECTION FOR THE RECEPTACLES |
| | INSTALLED WITHIN 6 FT OF THE OUTSIDE EDGE OF THE SINK. |
| | 210.8(B)(5) |
| | |
| | 5) PROVIDE A LIGHTING PLAN AND INCLUDE THE EGRESS |
| | LIGHTING REQUIRED BY NFPA 101 SECTION 7.10.1.5.1 |
| | |
| | 6) INDICATE THE REQUIRED CIRCUITRY FEEDING THE EGRESS |
| | LIGHTING IN COMPLIANCE WITH THE NEC 700.12 |
| | |
| | 7) INDICATE THE REQUIRED SIGN CIRCUIT IN COMPLIANCE |
| | WITH THE NEC 600.5 AND TIMER IN COMPLIANCE WITH THE |
| | FBC-E 505.2. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |