2015-12-02 16:26:031ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
  
  
 1- WRONG GEC SIZE FOR SERVICE PLEASE TAKE A LOOK AT
 TABLE 250.66 NEC
 2- WRONG OVERCURRENT DEVICE FOR DISCONNECT B AND C
 240.4 PROTECTION OF CONDUCTORS. CONDUCTORS, OTHER THAN
 FLEXIBLE CORDS, FLEXIBLE CABLES, AND FIXTURE WIRES,
 SHALL BE
 PROTECTED AGAINST OVERCURRENT IN ACCORDANCE WITH THEIR
 AMPACITIES
 SPECIFIED IN 310.15
 3-AC DISCONNECTS NOT DRAWN READILY ACCESIBLE
 440.14 LOCATION. DISCONNECTING MEANS SHALL BE LOCATED
 WITHIN SIGHT FROM AND READILY ACCESSIBLE FROM THE
 AIRCONDITIONING
 OR REFRIGERATING EQUIPMENT.
 4-FIRST FLOOR ELECTRICAL PLAN SHOWS SWITCH INSIDE A
 DOOR OPENNIG ( TYPO)
 5-POOL EQUIPMENT DOESN'T SHOW GFCI PROTECTION
 440.14 LOCATION. DISCONNECTING MEANS SHALL BE LOCATED
 WITHIN SIGHT FROM AND READILY ACCESSIBLE FROM THE
 AIRCONDITIONING
 OR REFRIGERATING EQUIPMENT.
 6-ISLAND RECEPTACLES DOESN'T SHOW GFCI PROTECTION ?
 7-RECESSD LIGHTS ARE NOT SHOWN TO BE IC RATED ?
 8-PLEASE PROVIDE MOUNTING DETAIL FOR FLOURESECENT
 FIXTURES ON FIRST FLOOR GARAGE.
 9-PLEASE PROVIDE MANUFACTURE SPECS FOR CAR LIFTS AND
 ELEVATOR EQUIPMENT.
  