| 2015-10-28 12:18:57 | 2ND REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15061466 |
| | 10/28/15 |
| | |
| | SOME OF THE COMMENTS FROM THE 1ST REVIEW HAVE NOT BEEN |
| | COMPLETELY ADDRESSED ON THE PLANS. I AM REPRINTING |
| | THOSE COMMENTS IN THIS REVIEW. |
| | PLEASE PROVIDE: |
| | 1-D) AIR DISTRIBUTION SCHEDULE INDICATING MAKES, |
| | MODELS, AND DIMENSIONS OF DIFFUSERS AND GRILLS. |
| | 1-E) AC DUCT CONNECTION, SUPPORT AND HANGING DETAILS |
| | 1-I) VERIFICATION OF CONDENSER INSTALLATION AT OR ABOVE |
| | THE BASE FLOOD ELEVATION HEIGHT- SEE SECTION R322.1.6 |
| | FBC-14 RESIDENTIAL. |
| | 5) PROVIDE SIZING CALCULATIONS FOR THE EXHAUST |
| | VENTILATION SYSTEMS SHOWN IN THE THE GARAGE, BIKE SHOP, |
| | AND STORAGE AREA ON THE 1ST FLOOR. |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CARBON |
| | MONOXIDE DETECTORS AND INDICATE THEIR EXACT |
| | INSTALLATION LOCATIONS ON THE PLAN (SPACINGS, HEIGHT |
| | AFF). |
| | 7) SUBMIT FL. PRODUCT APPROVALS OR MIAMI-DADE NOA'S FOR |
| | THE EXHAUST AND MAKE UP AIR LOUVERS. |
| | 8) THE U-FACTORS SHOWN ON THE ENERGY CALCULATIONS FOR |
| | THE WINDOWS DO NOT MATCH THE VALUES LISTED ON THE AC |
| | CALCULATIONS. |
| | 9) THE OVERHEAD DOORS IN THE MAIN GARAGE AND STORAGE 3 |
| | ARE INDICATED AS WOOD DOORS ON THE ENERGY CALCS, |
| | HOWEVER THE NOA SUBMITTED FROM AMARR SHOWS THEM TO BE |
| | STEEL. ALSO NO DATA IS SHOWN ON THE CALCS FOR THE MAN |
| | DOOR IN THE GARAGE. |
| | |
| | CHRISTOPHER L. COLE |