Plan Review Notes
Plan Review Notes For Permit 15061466
Permit Number 15061466
Review Stop M
Sequence Number 2
Notes
Date Text
2015-10-28 12:18:572ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15061466
 10/28/15
  
 SOME OF THE COMMENTS FROM THE 1ST REVIEW HAVE NOT BEEN
 COMPLETELY ADDRESSED ON THE PLANS. I AM REPRINTING
 THOSE COMMENTS IN THIS REVIEW.
 PLEASE PROVIDE:
 1-D) AIR DISTRIBUTION SCHEDULE INDICATING MAKES,
 MODELS, AND DIMENSIONS OF DIFFUSERS AND GRILLS.
 1-E) AC DUCT CONNECTION, SUPPORT AND HANGING DETAILS
 1-I) VERIFICATION OF CONDENSER INSTALLATION AT OR ABOVE
 THE BASE FLOOD ELEVATION HEIGHT- SEE SECTION R322.1.6
 FBC-14 RESIDENTIAL.
 5) PROVIDE SIZING CALCULATIONS FOR THE EXHAUST
 VENTILATION SYSTEMS SHOWN IN THE THE GARAGE, BIKE SHOP,
 AND STORAGE AREA ON THE 1ST FLOOR.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CARBON
 MONOXIDE DETECTORS AND INDICATE THEIR EXACT
 INSTALLATION LOCATIONS ON THE PLAN (SPACINGS, HEIGHT
 AFF).
 7) SUBMIT FL. PRODUCT APPROVALS OR MIAMI-DADE NOA'S FOR
 THE EXHAUST AND MAKE UP AIR LOUVERS.
 8) THE U-FACTORS SHOWN ON THE ENERGY CALCULATIONS FOR
 THE WINDOWS DO NOT MATCH THE VALUES LISTED ON THE AC
 CALCULATIONS.
 9) THE OVERHEAD DOORS IN THE MAIN GARAGE AND STORAGE 3
 ARE INDICATED AS WOOD DOORS ON THE ENERGY CALCS,
 HOWEVER THE NOA SUBMITTED FROM AMARR SHOWS THEM TO BE
 STEEL. ALSO NO DATA IS SHOWN ON THE CALCS FOR THE MAN
 DOOR IN THE GARAGE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  