Plan Review Notes
Plan Review Notes For Permit 15061466
Permit Number 15061466
Review Stop B
Sequence Number 2
Notes
Date Text
2015-11-03 15:27:58NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-RESIDENTIAL -5TH EDITION(2014.
  
 1- THE 2014 BC TOOK EFFECT ON JUNE 30TH, 2015. PERMIT
 APPLICATION WAS SUBMITTED ON JUNE 30TH. BUILDING REVIEW
 WILL BE DONE BASED ON THE NEW CODE. PLEASE UPDATE ALL
 PLANS AND NOTES AS REQUIRED.
 RESPONSE: SHEET A0 WAS NOT REVISED. STILL REFERENCING
 THE 2010 CODE.
  
 2- ARCHITECTURAL PLANS TITLE BLOCK IS MISSING ALL THE
 INFORMATION OF THE ARCHITECT WHO IS SIGNING AND SEALING
 THE PLANS AS REQUIRED BY FAC 61G1-16.004.
 RESPONSE: TITLE BLOCK WAS NOT REVISED. THE ARCHITECT'S
 REQUIRED INFORMATION STILL NO PROVIDED.
  
 3- A) SOIL TEST REPORT SUBMITTED: PROJECT DESCRIPTION
 DOESN'T MATCH PROPOSED CONSTRUCTION. BUILDING AREA IS
 SIGNIFICANTLY HIGHER AND THE TYPE OF PROPOSED
 CONSTRUCTION NEEDS ATTENTION TOO. REVISE REPORT AS
 REQUIRED. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 B) ENGINEER OF RECORD TO REVIEW REVISED SOIL TEST
 REPORT BASED ON THE ACTUAL PROPOSED CONSTRUCTION AND
 SQUARE FOOTAGE. AND, ACKNOWLEDGE IN WRITING TO THIS
 OFFICE THAT GEOTECHNICAL FOUNDATION RECOMMENDATIONS
 WERE ADOPTED IN THE DESIGN, INCLUDING THE
 RECOMMENDATION TO STRUCTURALLY SEPARATE FOOTING AND
 COLUMNS FROM THE FLOOR SLAB. OTHERWISE, PROVIDE
 ENGINEERING ANALYSIS FOR PROPOSED FOOTING DESIGN SHOWN
 ON PLANS. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 4- NEW ELEVATOR/FLOOD ZONE NOTE ON SHEET A6: CODE SEC.
 R1403.5. & 6 SPECIFIED ON NOTE #1 DOESN'T EXIST ON THE
 2014 CODE AND DOESN'T APPLY TO ELEVATOR EQUIPMENT.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- REVISE FOUNDATION PLAN ON SHEET S1 TO MATCH REVISED
 ARCHITECTURAL PLAN SHOWING LANDING FROM THE CLUB ROOM
 TO THE COVERED LANAI AS REQUIRED BY SEC. R311.3 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 6- PROVIDE DETAILS AND SPECIFICATIONS FOR THE DESIGN OF
 THE STRUCTURAL SUPPORTS OF THE ELEVATOR AS REQUIRED BY
 ELEVATOR SPECS SUBMITTED AND SEC. R301 FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 7- PROVIDE COMPLIANCE WITH THE ACCESSIBILITY SEC. R320.
 RESPONSE: 2'-6" DOORS DON'T PROVIDE 29" CLEAR OPENING.
  
 8- SHEET A6: SPECIFY OVERFLOW DRAINS OR SCUPPERS AS
 REQUIRED BY SEC. R903.4.1.
 RESPONSE: OVERFLOW DRAINS WERE NOT SPECIFIED. THESE ARE
 ADDITIONAL TO THE REGULAR FLOOR DRAINS. SEE SEC. R903.1
  
 9- SHEET A7: SPECIFY OVERFLOW DRAINS OR SCUPPERS AS
 REQUIRED BY SEC. R903.4.1.
 RESPONSE: OVERFLOW DRAINS WERE NOT SPECIFIED. THESE ARE
 ADDITIONAL TO THE REGULAR FLOOR DRAINS. SEE SEC. R903.1
  
 10- PROVIDE ICC EVALUATION REPORT FOR THE SPRAY
 INSULATION SPECIFIED ON PLANS. SEC. R316.
 RESPONSE: EVALUATION REPORT ESR-1826 SUBMITTED EXPIRED
 ON FEBRUARY 1, 2015. NEED CURRENT ONE. REMAINDER: AND,
 ARCHITECT TO APPROVE PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 11- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) ROOF INFORMATION ON PAGE 3 OF 7: REVISE ROOF TYPE
 AND MATERIALS TO MATCH PLANS. PLANS SHOW MODIFIED
 BITUMEN AND METAL ROOF. SEC. R101.5.1.1.2 OF FBC-
 ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE: INFORMATION IS INCORRECT. THE FLAT ROOF IS
 NOT METAL. THE FLAT ROOF IS MODIFIED BITUMEN AND THERE
 IS A PITCHED ROOF WITH METAL ROOF. SEE PLANS AND REVISE
 AS REQUIRED.
  
 B) CEILING INFORMATION ON PAGE 3 OF 7: R VALUE TO MATCH
 PLANS AND PAGE 1 OF 7. SEC. R101.5.1.1.2 OF FBC- ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: INFORMATION SUBMITTED STILL DOESN'T MATCH.
  
 C) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS
 REQUIRED BY SEC. R103.1.1.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 D) REVISE THE CLIMATE ZONE ON PAGE 2 OF 6. PALM BEACH
 IS NOT ZONE 2.. SEE TABLE R301.1 OF FBC- ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 NOTE:
 LABEL FOR THE WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE DEFAULT FACTOR FOR GLAZING.
  
 12- REVISED HANDRAIL DETAIL TO SHOW COMPLIANCE WITH THE
 OPENING LIMITATIONS OF THE TRIANGULAR AREA FORMED BY
 THE TREAD, RISER AND BOTTOM OF RAIL AS REQUIRED SEC.
 R312.1.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) CUSTOM ENTRY DOOR AS SHOWN ON PLANS. PROVIDE
 COMPLETE ENGINEERING PACKAGE FOR BUILDING OFFICIAL
 APPROVAL. CONTACT BROWN AT [email protected].
 RESPONSE: IT WILL BE SUBMITTED AT A FUTURE DATE PRIOR
 TO INSTALLATION. OK.
  
 B) STEEL PANEL WALL SYSTEM AS SHOWN ON PLANS.
 RESPONSE: WILL BE SUBMITTED LATER. OK.
  
 C) 14" EXHAUST AIR GRILLS AS SHOWN ON PLANS.
 RESPONSE: PROVIDE THE ACTUAL MIAMI-DADE NOA OR FLORIDA
 PRODUCT APPROVAL. AND DESIGNER OF RECORD TO APPROVE
 BEFORE SUBMITTAL TO THIS OFFICE.
  
 D) METAL ROOF AS SHOWN ON PLANS.
 RESPONSE: TO BE SUBMITTED LATER. OK.
  
 E) MODIFIED ROOFING FOR LOW SLOPE ROOF AS SHOWN ON
 PLANS. AND, IDENTIFY SELECTED APPROVED ASSEMBLY. AND
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE CALCULATED DESIGN
 PRESSURES.
 RESPONSE: TO BE SUBMITTED LATER. OK.
  
 14- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
 NOTE: PLEASE PLACE THE REVIEW STAMP ON THE FRONT OF THE
 PRODUCT APPROVAL COVER PAGE NOT ON THE BACK (OR ON ANY
 OTHER FRONT PAGE WHERE THERE IS ENOUGH ROOM FOR THE
 STAMP). SCANNING DOCUMENTS FOR RECORD KEEPING IS NOT
 ADEQUATE WHEN STAMPS ARE ON THE BACK OF THE PAGE.
  
 15- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FINISH COVERING OF THE SECOND FLOOR COVERED TERRACE.
 SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE: TO BE SUBMITTED LATER. OK.
  
 16- PRIOR TO FABRICATION AND INSTALLATION PROVIDE
 COMPLETE ENGINEER PACKAGE FOR THE BAR JOIST AND
 CONCRETE DECK SYSTEMS, STAIRWAY , HANDRAILS AND
 GUARDRAILS APPROVED BY THE DESIGNER OF RECORD.
 RESPONSE: TO BE SUBMITTED LATER. OK.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPIES FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]