Plan Review Notes
Plan Review Notes For Permit 15061466
Permit Number 15061466
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-27 15:43:06 
 1. GARAGE SHOWS AUTOMOBILE LIFT AND ELECTRICAL BOXES
 NOTED AS "CAR EQUIPMENT" AN AIR COMPRESSOR, CARBON
 MONOXIDE SENSOR , ETC. THIS HAS ALL THE APPEARANCE OF A
 VEHICLE REPAIR FACILITY. WHICH FALLS UNDER AN S-1
 OCCUPANCY AND THE 2014 BC PLUMBING CODE.
  
 2A. WHERE ARE THE FLOOR DRAINS TERMINATING
 2B.AN OIL SEPARATOR IS REQUIRED PER 2014 FBC P 1003.4
 AND SHALL COMPLY WITH FBC P SEC. 1003.4.1 THRU
 1003.4.2.2 FLOOR DRAINS MUST DISCHARGE THRU OIL
 SEPARATOR.
  
 3.DOWNSPOUTS SHALL BE SIZED IN ACCORDANCE WITH 2014 FBC
 P TABLE 1106.2[2] SHEET A-9 INDICATE SIZE OF DOWNSPOUTS
 SQ FT. BEING DRAINED BY EACH DOWNSPOUT BASED ON 5IN.
 RAINFALL RATIO 1/2 THE AREA OF ANY VERTICAL THAT
 CONNECTS TO ROOF SHALL BE CALCULATED IN TH SQ. FT.
 CALCULATIONS.
  
 4.PLEASE INDICATE ON THE PLAN IF THE ELEVATOR IS
 TRACTION TYPE OR HYDRAULIC IF HYDRAULIC PIT MUST DRAIN
 THRU OIL SEPARATOR FBC 10004.3.
  
 5.SUBMIT POTABLE WATER RISER. PER WPB AMENDMENTS TO FBC
 2010 107.3.5.2
  
 6. INDICATE ON THE PLAN IF ANY COMPRESSED AIR PIPING
 WILL BE INSTALLED, IF SO SUBMIT A RISER DIAGRAM FOR AIR
 PIPING SHOW SUPPORT,SIZINGS TYPE OF PIPE USED ,VALVES
 AND OUTLETS ETC.
  
 7.SHEET A-10 BLDG. SEC A-A SHOWS HYDRAULIC LIFT PIT
 WITH TWO DRAIN PIPES WHAT IS THE USE OF THESE LINES
 ,ARE THEY PERFORATED PLEASE CLARIFY.
  
  
  
  
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  