| 2015-07-27 15:43:06 | |
| | 1. GARAGE SHOWS AUTOMOBILE LIFT AND ELECTRICAL BOXES |
| | NOTED AS "CAR EQUIPMENT" AN AIR COMPRESSOR, CARBON |
| | MONOXIDE SENSOR , ETC. THIS HAS ALL THE APPEARANCE OF A |
| | VEHICLE REPAIR FACILITY. WHICH FALLS UNDER AN S-1 |
| | OCCUPANCY AND THE 2014 BC PLUMBING CODE. |
| | |
| | 2A. WHERE ARE THE FLOOR DRAINS TERMINATING |
| | 2B.AN OIL SEPARATOR IS REQUIRED PER 2014 FBC P 1003.4 |
| | AND SHALL COMPLY WITH FBC P SEC. 1003.4.1 THRU |
| | 1003.4.2.2 FLOOR DRAINS MUST DISCHARGE THRU OIL |
| | SEPARATOR. |
| | |
| | 3.DOWNSPOUTS SHALL BE SIZED IN ACCORDANCE WITH 2014 FBC |
| | P TABLE 1106.2[2] SHEET A-9 INDICATE SIZE OF DOWNSPOUTS |
| | SQ FT. BEING DRAINED BY EACH DOWNSPOUT BASED ON 5IN. |
| | RAINFALL RATIO 1/2 THE AREA OF ANY VERTICAL THAT |
| | CONNECTS TO ROOF SHALL BE CALCULATED IN TH SQ. FT. |
| | CALCULATIONS. |
| | |
| | 4.PLEASE INDICATE ON THE PLAN IF THE ELEVATOR IS |
| | TRACTION TYPE OR HYDRAULIC IF HYDRAULIC PIT MUST DRAIN |
| | THRU OIL SEPARATOR FBC 10004.3. |
| | |
| | 5.SUBMIT POTABLE WATER RISER. PER WPB AMENDMENTS TO FBC |
| | 2010 107.3.5.2 |
| | |
| | 6. INDICATE ON THE PLAN IF ANY COMPRESSED AIR PIPING |
| | WILL BE INSTALLED, IF SO SUBMIT A RISER DIAGRAM FOR AIR |
| | PIPING SHOW SUPPORT,SIZINGS TYPE OF PIPE USED ,VALVES |
| | AND OUTLETS ETC. |
| | |
| | 7.SHEET A-10 BLDG. SEC A-A SHOWS HYDRAULIC LIFT PIT |
| | WITH TWO DRAIN PIPES WHAT IS THE USE OF THESE LINES |
| | ,ARE THEY PERFORATED PLEASE CLARIFY. |
| | |
| | |
| | |
| | |
| | |
| | 1ST REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | 561-805-6711 |
| | [email protected] |
| | |