Plan Review Notes
Plan Review Notes For Permit 15061466
Permit Number 15061466
Review Stop M
Sequence Number 1
Notes
Date Text
2015-09-11 16:28:341ST REVIEW: FBC 2014 RESIDENTIAL
 PERMIT #15061466
 9/11/15
  
 1) SUBMIT COMPLETE MECHANICAL PLANS, DETAILS, AND
 SPECIFICATIONS FOR REVIEW INCLUDING:
 A) AC DUCT LAYOUT PLANS FOR EACH NEW SYSTEM INDICATING
 THE TYPES AND SIZES OF DUCTS, SUPPLY CFM'S AT EACH
 DIFFUSER, MEANS OF RETURN AIR INCLUDING DIMENSIONS OF
 RETURN AIR GRILLS, TRANSFER GRILLS, AND RETURN CFM'S.
 REFER TO SECTION M1602.2 FOR PROHIBITED RETURN AIR
 SOURCES.
 B) AC EQUIPMENT SCHEDULES LISTING THE MAKES AND MODELS
 OF ALL COMPONENTS, COOLING AND HEATING CAPACITIES,
 EFFICIENCY RATINGS, ELECTRICAL DATA ETC.
 C) AHRI CERTIFICATES FOR EACH NEW SYSTEM.
 D) AIR DISTRIBUTION SCHEDULE INDICATING MAKES, MODELS,
 AND DIMENSIONS OF DIFFUSERS AND GRILLS.
 E) AC DUCT CONNECTION, SUPPORT AND HANGING DETAILS
 F) DIMENSIONED PLAN AND SECTION VIEWS OF THE AIR
 HANDLER CLOSET INDICATING COMPLIANCE WITH SECTION
 M1305.1.1 FBC-14 RESIDENTIAL, AND SECTION C403.2.7.2
 FBC-14 ENERGY CONSERVATION- SHOW THE MEANS OF RETURN
 AIR TO EACH UNIT IN THE CLOSET.
 G) CONDENSATE DISPOSAL PLANS- PRIMARY AND SECONDARY FOR
 EACH NEW AIR HANDLER- SEE SECTION M1411.3 RESIDENTIAL.
 H) WIND LOAD TIE DOWN ENGINEERING FOR MOUNTING THE AC
 CONDENSERS TO THE NEW PADS- SEE SECTIONS M1305.1.4.1 &
 M1307.2 FBC-14 RESIDENTIAL
 I) VERIFICATION OF CONDENSER INSTALLATION AT OR ABOVE
 THE BASE FLOOD ELEVATION HEIGHT- SEE SECTION R322.1.6
 FBC-14 RESIDENTIAL.
 2) PROVIDE BATHROOM EXHAUST DETAILS: EXHAUST FAN
 EQUIPMENT SCHEDULES, EXHAUST DUCT RUNS AND TERMINATION
 LOCATIONS.
 3) PROVIDE DRYER EXHAUST AND MAKEUP AIR PLANS PER
 SECTION M1502: SHOW THE TYPE AND SIZE OF EXHAUST DUCT,
 EXHAUST DUCT RUN LENGTH AND TERMINATION LOCATION, AND
 INDICATE HOW MAKEUP AIR WILL BE SUPPLIED TO EACH DRYER.
 SUBMIT MANUFACTURER'S SPECS FOR THE APPLIANCES.
 4) REFER TO SECTION M1503 AND PROVIDE KITCHEN EXHAUST
 VENTILATION PLANS.
 5) PROVIDE SIZING CALCULATIONS FOR THE EXHAUST
 VENTILATION SYSTEMS SHOWN IN THE THE GARAGE, BIKE SHOP,
 AND STORAGE AREA ON THE1ST FLOOR.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CARBON
 MONOXIDE DETECTORS AND INDICATE THEIR EXACT
 INSTALLATION LOCATIONS ON THE PLAN (SPACINGS, HEIGHT
 AFF).
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT
 APPROVALS FOR THE EXHAUST AND MAKE UP AIR FANS AND
 LOUVERS. PROVIDE FAN SCHEDULES ON THE PLANS INDICATING
 THEIR CFM CAPACITIES, ELECTRICAL DATA ETC.
 PLEASE NOTE ADDITIONAL COMMENTS MAY FOLLOW SUBMITTAL OF
 REVISED PLANS AND RESPONSES TO ALL BUILDING DEPARTMENT
 COMMENTS.
  