| Plan Review Notes For Permit 15061462 |
| Permit Number |
15061462 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-09-23 15:14:01 | 3RD REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15061462 | | | 9/23/15 | | | | | | 1) SHEET B-4: THE REVISED PLAN IS INDICATING A 23' | | | CLEARANCE DISTANCE FROM THE TWO PAINT BOOTH EXHAUST | | | DUCT TERMINATIONS TO TO THE REAR PROPERTY LINE- MINIMUM | | | 30' CLEARANCE IS REQUIRED IN ACCORDANCE WITH SECTION | | | 501.3.1 FBC-10 MECHANICAL ITEM #1. PLEASE RELOCATE THE | | | TERMINATIONS TO BE IN COMPLIANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|