| Plan Review Notes For Permit 15061462 |
| Permit Number |
15061462 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-07 14:56:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) PROVIDE BOOTH MANUFACTURER'S SPEC SHEETS. | | | | | | 2) PROVIDE MANUFACTURER'S JUSTIFICATION FOR APPLYING | | | THE EXCEPTION FOR 3' SPACE AROUND THE SIDES OF THE | | | BOOTHS. | | | | | | 3) HOW WOULD A REPAIR TAKE PLACE ALONG A WALL SECTION | | | AGAINST A WALL? | | | | | | 4) HOW WOULD THE ACCUMULATION OF DUST AND DEBRI TAKE | | | PLACE ALONG A WALL SECTION AGAINST A WALL? | | | | | | 5) THE MIXING ROOM SHALL COMPLY WITH ALL REQUIRMENTS OF | | | NFPA 33 8.3, | | | | | | 6) PROVIDE DIMENSIONS OF THE MIXING ROOM | | | | | | 7) PROVIDED THE MIXING ROOM WITH A AUTOMATIC FIRE | | | PROTECTION SYSTEM. | | | | | | 8) PROVIDE A FE INSIDE THE MIXING ROOM. PER NFPA 10 | | | | | | | | | |
|