| 2015-07-27 14:54:20 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:15061462 |
| | ADD: 1500 CLARE AVE. |
| | CONT: FLORIDA FILTRATION |
| | TEL: (561)582-5543 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 27/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PLAN LABELED B-1 SHOWS THE SPRAY BOOTH AGAINST |
| | THE EXTERIOR WALL. THE 2014 FBC-B 416.4 SPRAY BOOTHS |
| | SHALL BE DESIGNED, CONSTRUCTED AND OPERATED IN |
| | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. THE |
| | PLAN SHOWS THE SPRAY BOOTH AGAINST THE EXTERIOR WALLS. |
| | NFPA 33 5.3 REQUIRES THE SPRAY BOOTH TO BE A 1 HOUR |
| | CONSTRUCTION AND AT LEAST 3 FEET AWAY FROM THE EXTERIOR |
| | WALL. EXCEPTION # 2 WILL ALLOW THE UNIT TO BE CLOSER |
| | THAN 3 FT IF THE SPRAY BOOTH CAN BE MAINTAINED AND |
| | CLEANED. PLEASE PROVIDE THE MANUFACTURERS |
| | SPECIFICATIONS FOR THE ONE HOUR FIRE RATING AS WELL AS |
| | SHOWING HOW THE UNIT WILL BE MAINTAINED AND KEPT CLEAN. |
| | |
| | 2) SHEET B-2 SHOWS A DETAIL WHERE CEILING JOIST/ |
| | RAFTERS WITH ONE CEILING JOIST/ RAFTER IS CUT AND |
| | HEADERS ATTACHED. THE PLANS FAIL TO SHOW COMPLIANCE |
| | WITH 2014 FBC-B 2308.10.4.3 FRAMING AROUND HOLES. |
| | TRIMMERS AND HEADERS RAFTERS SHALL BE DOUBLED, OR OF |
| | LUMBER OF EQUIVALENT CROSS SECTION, WHERE THE SPAN OF |
| | THE HEADER EXCEEDS 4 FEET. THE PLANS DO NOT INDICATE |
| | WHAT THE DOUBLE LINES REPRESENT, THE OUTER BAND IS PAST |
| | THE FRAMING MEMBER WHICH WILL REQUIRE THE FRAMING |
| | HEADER TO GO TO THE NEXT RAFTER. THE PLANS ALSO WILL |
| | NEED TO INDICATE THE TYPE OF HANGER/ BUCKET TO BE USED |
| | IN THIS INSTALATION FOR BOTH THE HEADER AND THE CUT |
| | RAFTERS. |
| | |