2015-10-27 14:27:5510/27/15 MET W/ OWNER AND CONTRACTOR. BECAUSE OF PLAN
 REVIEW WORK LOAD I OFFER THEM THE OPTION OF PROVISO.
 THEY AGREED FOR ISSUANCE OF PERMIT WITH PROVISO. THEY
 WILL SUBMIT ALL THE REQUIRED INFORMATION AFTER THE
 PERMIT IS ISSUED. ADVISED THEM FEES WOULD APPLY AND TO
 SUBMIT INFORMATION BEFORE INSPECTIONS TO AVOID
 CONFLICTS OR DELAYS. JG.
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- DESIGNER OF RECORD TO SPECIFY ON PLANS ROOF TILE
 FASTENING. SEC. 107.2.1.2 CITY AMENDMENTS.
 2- SHEET A.05: CODES SPECIFIED ON THE DRAINAGE
 CALCULATIONS ARE MISMATCHED. REVISE AS REQ'D.
 3- DETAIL 3/A.06: SPECIFY HANDRAIL HEIGHT & OPENING
 LIMITATIONS. SEC. R311.7.8 & SEC. R312.1.3
 4- SPECIFY ROOF VENTILATION FOR THE NEW CARRIAGE HOUSE
 & NEW FLORIDA ROOM. SEC. R806. IF DESIGNING UNVENTED
 ATTIC, PROVIDE SPECS AS REQ'D BY SEC. R806.5 . PROVIDE
 ICC EVALUATION REPORT REVIEWED BY THE ARCHITECT IF
 USING FOAM INSULATION.
 5- SHEET S-1:
 A) CODE IN EFFECT IS THE FBC-5TH EDITION (2014). REVISE
 PLANS AS REQUIRED.
 B) DETAIL 8/S-1: PROVIDE COMPLETE DETAIL THAT MATCHES
 EXTERIOR ELEVATIONS. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE FRAMING OF THE PARAPET WALLS.
 ALSO, REVISE SIZE OF ROOF TRUSSES TO MATCH: 12" OR 16"
 TRUSSES?. SEC. R301. .
 C) REVISE ROOF SHEATHING SPECIFICATIONS SHOWN ON THE
 MAIN HOUSE COVERED PORCH ROOF FRAMING PLAN. NEED TO
 SPECIFY MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1 OR PROVIDE ENGINEERING ANALYSIS SHOWING THAT
 10D COMMON NAILS ARE EQUIVALENT TO THE 8D RING SHANK
 NAILS. SEC. 107.2.1.3 CITY AMENDMENTS. NOTE: THIS
 APPLIES TO THE CARRIAGE HOUSE ALSO.
 D) PROVIDE COMPLETE DOOR AND WINDOW FRAMING DETAILS FOR
 ALL NEW DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SEC. R301.
 E) WALL SECTIONS: SPECIFY 6" MIN. CLEARANCE FROM GRADE
 AS REQUIRED BY SEC. R404.1.6.
 F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 COLUMNS CONNECTIONS AT TOP AND BOTTOM. SPECIFY ALL
 PLATES SIZES, LENGTH AND NUMBER OF ANCHORS AND ALL TOP
 CONNECTORS. SEC. R301.
 G) COVERED PORCH ROOF FRAMING PLAN: SPECIFY CONNECTORS
 AT THE ENDS OF ALL WOOD BEAMS AND GIRDER TRUSS SHOWN
 NEXT TO THE EXISTING WALL. SEC. R301.
 6- SHEET S-2:
 A) UPDATE THE "BASIS OF DESIGN" INFORMATION. REFER TO
 CURRENT CODE 2014. REVISE BUILDING EXPOSURE ACCORDING
 TO THE LOCATION OF BUILDING AND THE WIND VELOCITY. SEC.
 R301.
 B) OUTRIGGER DETAIL: SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.
 C) SITE WALL DETAIL. (1)THERE ARE TWO DIFFERENT HEIGHTS
 SHOWN ON PLANS. REVISE AS REQUIRED TO MATCH PLANS. SEC.
 107.2.1 CITY AMENDMENTS. (2)PROVIDE EMBEDMENT DEPTH OR
 PROVIDE GEOTECHNICAL REPORT AS SPECIFIED ON THE DETAIL.
 SEC. R301. (3)PROVIDE MANUFACTURER'S SPECS FOR THE
 SPECIFIED HELICAL CONNECTORS.
 D) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS PROJECT
 TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) CONCRETE TILE ADHESIVE IF SPECIFIED BY THE DESIGNER
 OF RECORD. SEE CONCRETE TILE NOA FOR LISTED ADHESIVES.
 B) SLIDING GLASS DOORS AS SHOWN ON PLANS. PROVIDE
 PRODUCT APPROVAL THAT MATCHES PLANS AND THAT MEETS THE
 DESIGN PRESSURES CALCULATED BY THE DESIGNER OF RECORD.
 FLORIDA PRODUCT APPROVAL FL15232-R1 SUBMITTED DOESN'T
 MATCH DOORS SHOWN ON PLANS AND DOESN'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD.
 C) NEW STORAGE DOORS AS SHOWN ON PLANS.
 D) NEW CRAWL SPACE ACCESS DOOR AS SHOWN ON PLANS.
 E) FLAT ROOF. AND CLEARLY IDENTIFY APPROVED ASSEMBLY TO
 BE INSTALLED. AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF REQUIRED BY THE PRODUCT APPROVAL
 SUBMITTED TO MEET THE CALCULATED DESIGN PRESSURES. SEC.
 R301.
 F) CASEMENT WINDOW SIZE AS SHOWN ON PLANS AND WINDOW
 SCHEDULE FOR WINDOW W20. FLORIDA PRODUCT APPROVAL
 FL15190-R1 SUBMITTED DOESN'T COVER THIS WINDOW WIDTH.
 8- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
 9-DESIGNER OF RECORD TO APPROVE A/C PLAN DESIGN AND
 APPROVE AND SPECIFY LOUVERED DOOR FOR THE BEDROOM IN
 THE CARRIAGE HOUSE. BALANCED RETURN AIR WAS DESIGNED TO
 BE ACCOMPLISHED WITH LOUVERED DOOR. SEC. M1602.4