| Date |
Text |
| 2015-10-27 14:27:55 | 10/27/15 MET W/ OWNER AND CONTRACTOR. BECAUSE OF PLAN |
| | REVIEW WORK LOAD I OFFER THEM THE OPTION OF PROVISO. |
| | THEY AGREED FOR ISSUANCE OF PERMIT WITH PROVISO. THEY |
| | WILL SUBMIT ALL THE REQUIRED INFORMATION AFTER THE |
| | PERMIT IS ISSUED. ADVISED THEM FEES WOULD APPLY AND TO |
| | SUBMIT INFORMATION BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS OR DELAYS. JG. |
| | |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- DESIGNER OF RECORD TO SPECIFY ON PLANS ROOF TILE |
| | FASTENING. SEC. 107.2.1.2 CITY AMENDMENTS. |
| | 2- SHEET A.05: CODES SPECIFIED ON THE DRAINAGE |
| | CALCULATIONS ARE MISMATCHED. REVISE AS REQ'D. |
| | 3- DETAIL 3/A.06: SPECIFY HANDRAIL HEIGHT & OPENING |
| | LIMITATIONS. SEC. R311.7.8 & SEC. R312.1.3 |
| | 4- SPECIFY ROOF VENTILATION FOR THE NEW CARRIAGE HOUSE |
| | & NEW FLORIDA ROOM. SEC. R806. IF DESIGNING UNVENTED |
| | ATTIC, PROVIDE SPECS AS REQ'D BY SEC. R806.5 . PROVIDE |
| | ICC EVALUATION REPORT REVIEWED BY THE ARCHITECT IF |
| | USING FOAM INSULATION. |
| | 5- SHEET S-1: |
| | A) CODE IN EFFECT IS THE FBC-5TH EDITION (2014). REVISE |
| | PLANS AS REQUIRED. |
| | B) DETAIL 8/S-1: PROVIDE COMPLETE DETAIL THAT MATCHES |
| | EXTERIOR ELEVATIONS. PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE FRAMING OF THE PARAPET WALLS. |
| | ALSO, REVISE SIZE OF ROOF TRUSSES TO MATCH: 12" OR 16" |
| | TRUSSES?. SEC. R301. . |
| | C) REVISE ROOF SHEATHING SPECIFICATIONS SHOWN ON THE |
| | MAIN HOUSE COVERED PORCH ROOF FRAMING PLAN. NEED TO |
| | SPECIFY MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC. |
| | R803.2.3.1 OR PROVIDE ENGINEERING ANALYSIS SHOWING THAT |
| | 10D COMMON NAILS ARE EQUIVALENT TO THE 8D RING SHANK |
| | NAILS. SEC. 107.2.1.3 CITY AMENDMENTS. NOTE: THIS |
| | APPLIES TO THE CARRIAGE HOUSE ALSO. |
| | D) PROVIDE COMPLETE DOOR AND WINDOW FRAMING DETAILS FOR |
| | ALL NEW DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS |
| | AND CONNECTORS. SEC. R301. |
| | E) WALL SECTIONS: SPECIFY 6" MIN. CLEARANCE FROM GRADE |
| | AS REQUIRED BY SEC. R404.1.6. |
| | F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL |
| | COLUMNS CONNECTIONS AT TOP AND BOTTOM. SPECIFY ALL |
| | PLATES SIZES, LENGTH AND NUMBER OF ANCHORS AND ALL TOP |
| | CONNECTORS. SEC. R301. |
| | G) COVERED PORCH ROOF FRAMING PLAN: SPECIFY CONNECTORS |
| | AT THE ENDS OF ALL WOOD BEAMS AND GIRDER TRUSS SHOWN |
| | NEXT TO THE EXISTING WALL. SEC. R301. |
| | 6- SHEET S-2: |
| | A) UPDATE THE "BASIS OF DESIGN" INFORMATION. REFER TO |
| | CURRENT CODE 2014. REVISE BUILDING EXPOSURE ACCORDING |
| | TO THE LOCATION OF BUILDING AND THE WIND VELOCITY. SEC. |
| | R301. |
| | B) OUTRIGGER DETAIL: SPECIFY ALL FRAMING MEMBERS AND |
| | CONNECTORS. SEC. R301. |
| | C) SITE WALL DETAIL. (1)THERE ARE TWO DIFFERENT HEIGHTS |
| | SHOWN ON PLANS. REVISE AS REQUIRED TO MATCH PLANS. SEC. |
| | 107.2.1 CITY AMENDMENTS. (2)PROVIDE EMBEDMENT DEPTH OR |
| | PROVIDE GEOTECHNICAL REPORT AS SPECIFIED ON THE DETAIL. |
| | SEC. R301. (3)PROVIDE MANUFACTURER'S SPECS FOR THE |
| | SPECIFIED HELICAL CONNECTORS. |
| | D) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS PROJECT |
| | TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS. |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) CONCRETE TILE ADHESIVE IF SPECIFIED BY THE DESIGNER |
| | OF RECORD. SEE CONCRETE TILE NOA FOR LISTED ADHESIVES. |
| | B) SLIDING GLASS DOORS AS SHOWN ON PLANS. PROVIDE |
| | PRODUCT APPROVAL THAT MATCHES PLANS AND THAT MEETS THE |
| | DESIGN PRESSURES CALCULATED BY THE DESIGNER OF RECORD. |
| | FLORIDA PRODUCT APPROVAL FL15232-R1 SUBMITTED DOESN'T |
| | MATCH DOORS SHOWN ON PLANS AND DOESN'T MEET THE DESIGN |
| | PRESSURES CALCULATED BY THE ENGINEER OF RECORD. |
| | C) NEW STORAGE DOORS AS SHOWN ON PLANS. |
| | D) NEW CRAWL SPACE ACCESS DOOR AS SHOWN ON PLANS. |
| | E) FLAT ROOF. AND CLEARLY IDENTIFY APPROVED ASSEMBLY TO |
| | BE INSTALLED. AND PROVIDE SIGNED AND SEALED RAS 117 |
| | CALCULATIONS IF REQUIRED BY THE PRODUCT APPROVAL |
| | SUBMITTED TO MEET THE CALCULATED DESIGN PRESSURES. SEC. |
| | R301. |
| | F) CASEMENT WINDOW SIZE AS SHOWN ON PLANS AND WINDOW |
| | SCHEDULE FOR WINDOW W20. FLORIDA PRODUCT APPROVAL |
| | FL15190-R1 SUBMITTED DOESN'T COVER THIS WINDOW WIDTH. |
| | 8- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT |
| | APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | 9-DESIGNER OF RECORD TO APPROVE A/C PLAN DESIGN AND |
| | APPROVE AND SPECIFY LOUVERED DOOR FOR THE BEDROOM IN |
| | THE CARRIAGE HOUSE. BALANCED RETURN AIR WAS DESIGNED TO |
| | BE ACCOMPLISHED WITH LOUVERED DOOR. SEC. M1602.4 |