2015-10-22 07:51:48RESIDENTIAL (R3) ADDITION/ALTERATION SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED. SEE
 BUILDING COMMENTS FOR REVISIONS REQUIRED ON THE ENERGY
 CALCULATIONS. NEED TO REVISE THE WALL TYPE AND NUMBER
 OF PEOPLE FOR A 1 BEDROOM UNIT. SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS AND DELAYS.
  
 2- DRAWING M.01 SUBMITTED NEEDS TO HAVE THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS
 REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS. REPEAT
 COMMENT.
  
 3- THE BEDROOM NEEDS TO COMPLY WITH THE BALANCED RETURN
 AIR SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). MECHANICAL PLAN INDICATES A LOUVERED DOOR FOR
 THE BEDROOM. LOUVERED DOOR IS NOT SPECIFIED BY THE
 ARCHITECT FOR THE BEDROOM. BESIDES, A LOUVERED DOOR FOR
 THE BEDROOM IS NOT VERY PRACTICAL AND MAY BE REPLACED.
 THEREFORE IS NOT ACCEPTABLE. THE BALANCED RETURN AIR IS
 TYPICAL DONE BY INSTALLING TRANSFER GRILLS OR TRANSFER
 DUCTS. SEE SEC. M1602.4 AND REVISE AS REQUIRED. REPEAT
 COMMENT.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPIES FOR REFERENCE.
  