2015-10-21 15:47:36RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF USING
 SCREWS/NAILS, THEN SPECIFY SIZE AND NUMBER.
  
 RESPONSE:
 RESPONSE LETTER SAYS SEE NOA SPECIFYING ATTACHMENT. THE
 PRODUCT APPROVAL IS JUST TO SHOW COMPLIANCE WITH THE
 DESIGNER OF RECORD DESIGN SPECIFICATIONS. DESIGNER OF
 RECORD TO SPECIFY FASTENING METHOD AS REQUIRED BY SEC.
 107.2.1.2.
  
 2- SHEET A.05: CODES SPECIFIED ON THE DRAINAGE
 CALCULATIONS ARE MISMATCHED. CALCULATIONS CALL FOR FBC
 2010 AND FBC 2015. THERE IS NOT FBC 2015 AND THE
 CURRENT CODE IS THE FBC- RESIDENTIAL, 5TH EDITION
 (2014). REVISE AS REQUIRED.
  
 3- FRONT ENTRY STAIR DETAIL 3/A.06: RAILING TO COMPLY
 WITH SEC. R311.7.8 AND SEC. R312.1.3. SPECIFY HANDRAIL
 HEIGHT AND OPENING LIMITATIONS.
  
 4- SPECIFY ROOF VENTILATION FOR THE NEW CARRIAGE HOUSE
 AND FOR NEW FLORIDA ROOM (COVERED PORCH) DETAIL 3/A.11
 AS REQUIRED BY SEC. R806.
  
 RESPONSE:
 THERE IS NOT INFORMATION ON SHEET A.05 AS SPECIFIED ON
 RESPONSE LETTER.
  
 5- WINDOW AND DOOR SCHEDULES ON SHEET A.12: CLEARLY
 SPECIFY TYPE OF EACH WINDOW AND DOOR. FOR EXAMPLE
 CASEMENT WINDOW, SINGLE HUNG WINDOW, SLIDING GLASS
 DOOR, FRENCH DOOR ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 6- PROVIDE ENERGY CALCULATIONS FOR THE NEW CARRIAGE
 HOUSE AS REQUIRED BY SEC. 1106 OF FBC-EXISTING
 BUILDING, 5TH EDITION (2014).
 NOTE: PLANS AND ENERGY CALCULATIONS TO BE COORDINATED
 TO AVOID CONFLICTS OR DELAYS.
  
 RESPONSE;
 ENERGY CALCULATIONS SUBMITTED ARE INCORRECT. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). (1)WALLS ARE NOT CONCRETE BLOCK. (2)CLARIFY WHY
 ARE THERE 3 OCCUPANTS IN ONE BEDROOM CARRIAGE HOUSE?.
 (3)CLARIFY WHERE ON PLANS IS THE GABLE AREA SPECIFIED
 ON PAGE 2 OF 4?. (4)THE ROOFING MATERIAL IS NOT
 COMPOSITION SHINGLES. (5)CLARIFY WHY THE CEILING
 R-VALUE SHOWN ON PAGE 2 OF 4 IS 0.1?. (6) REVISE THE
 WINDOWS OVERHANG SEPARATION TO MATCH PLANS. SEE PLANS
 AND REVISE AS REQUIRED. ALSO, PROVIDE BUILDER'S NAME ON
 TOP OF FORM.
  
 NOTE: LABELS SHOWING THE WINDOWS AND DOORS U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED FOR INSPECTION.
  
 7- ENERGY CALCULATIONS CALL FOR CARRIAGE HOUSE TO HAVE
 UNVENTED ATTIC. PLANS TO PROVIDE SPECIFICATIONS SHOWING
 COMPLIANCE WITH UNVENTED ATTIC SEC. R806.5 OF
 FBC-RESIDENTIAL, 5TH EDITION. PROVIDE ICC EVALUATION
 REPORT FOR TYPE OF INSULATION SPECIFIED TO CLOSE THE
 BUILDING ENVELOPE (ICYNENE FOR EXAMPLE) AND ARCHITECT
 TO REVIEW AND APPROVE THE REPORT PRIOR TO SUBMITTAL TO
 THIS OFFICE.
  
 8- SHEET S-1:
 A) CODE IN EFFECT AS OF JUNE 30TH 2015 IS THE FBC-5TH
 EDITION (2014). REVISE PLANS AS REQUIRED.
  
 RESPONSE:
 RESPONSE LETTER SAID "PLANS REVISED TO REFLECT CHANGE".
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 B) DETAIL 8/S-1: PROVIDE COMPLETE DETAIL THAT MATCHES
 EXTERIOR ELEVATIONS. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE FRAMING OF THE PARAPET WALLS.
 ALSO, REVISE SIZE OF ROOF TRUSSES TO MATCH: 12" OR 16"
 TRUSSES?. SEC. R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 C) REVISE ROOF SHEATHING SPECIFICATIONS SHOWN ON THE
 MAIN HOUSE COVERED PORCH ROOF FRAMING PLAN. NEED TO
 SPECIFY MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1 OR PROVIDE ENGINEERING ANALYSIS SHOWING THAT
 10D COMMON NAILS ARE EQUIVALENT TO THE 8D RING SHANK
 NAILS. SEC. 107.2.1.3 CITY AMENDMENTS. NOTE: THIS
 APPLIES TO THE CARRIAGE HOUSE ALSO.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 D) PROVIDE COMPLETE DOOR AND WINDOW FRAMING DETAILS FOR
 ALL NEW DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SEC. R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 E) WALL SECTIONS: SPECIFY 6" MIN. CLEARANCE FROM GRADE
 AS REQUIRED BY SEC. R404.1.6.
 NOTE: COORDINATE WITH FOOTING SIZE MF-1.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 COLUMNS CONNECTIONS AT TOP AND BOTTOM. SPECIFY ALL
 PLATES SIZES, LENGTH AND NUMBER OF ANCHORS AND ALL TOP
 CONNECTORS. SEC. R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 G) COVERED PORCH ROOF FRAMING PLAN: SPECIFY CONNECTORS
 AT THE ENDS OF ALL WOOD BEAMS AND GIRDER TRUSS SHOWN
 NEXT TO THE EXISTING WALL. SEC. R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 9- SHEET S-2:
 A) UPDATE THE "BASIS OF DESIGN" INFORMATION. REFER TO
 CURRENT CODE 2014. REVISE BUILDING EXPOSURE ACCORDING
 TO THE LOCATION OF BUILDING AND THE WIND VELOCITY. SEC.
 R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 B) OUTRIGGER DETAIL: SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 C) SITE WALL DETAIL. (1)THERE ARE TWO DIFFERENT HEIGHTS
 SHOWN ON PLANS. REVISE AS REQUIRED TO MATCH PLANS. SEC.
 107.2.1 CITY AMENDMENTS. (2)PROVIDE EMBEDMENT DEPTH OR
 PROVIDE GEOTECHNICAL REPORT AS SPECIFIED ON THE DETAIL.
 SEC. R301. (3)PROVIDE MANUFACTURER'S SPECS FOR THE
 SPECIFIED HELICAL CONNECTORS.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 D) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS PROJECT
 TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) CONCRETE TILE ADHESIVE IF SPECIFIED BY THE DESIGNER
 OF RECORD. SEE CONCRETE TILE NOA FOR LISTED ADHESIVES.
  
 B) SLIDING GLASS DOORS AS SHOWN ON PLANS.
 RESPONSE: PROVIDE PRODUCT APPROVAL THAT MATCHES PLANS
 AND THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE
 DESIGNER OF RECORD. FLORIDA PRODUCT APPROVAL FL15232-R1
 SUBMITTED DOESN'T MATCH DOORS SHOWN ON PLANS AND
 DOESN'T MEET THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER OF RECORD.
  
 C) NEW STORAGE DOORS AS SHOWN ON PLANS. REPEAT
 COMMENT..
  
 D) NEW CRAWL SPACE ACCESS DOOR AS SHOWN ON PLANS.
 REPEAT COMMENT.
  
 E) FLAT ROOF. AND CLEARLY IDENTIFY APPROVED ASSEMBLY TO
 BE INSTALLED. AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF REQUIRED BY THE PRODUCT APPROVAL
 SUBMITTED TO MEET THE CALCULATED DESIGN PRESSURES. SEC.
 R301.
 RESPONSE: (1) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY
 FROM NOA 13-0529.14 SUBMITTED IS GOING TO BE INSTALLED
 AND PROVIDE SIGNED AND SIGNED RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES OF SEC. R301.
 (2) CLARIFY WHY SUBMITTING INSULATION ADHESIVE NOA
 12-0329.02. PLANS DON'T CALL FOR ANY INSULATED FLAT
 ROOF ASSEMBLY.
 (3) CLARIFY WHY SUBMITTING SHARKSKIN ROOF UNDERLAYMENT
 NOA 09-1123.02. WHERE IS THIS GOING TO BE INSTALLED?.
 WHICH PRODUCT APPROVAL IS LISTING THIS PRODUCT?. SEE
 GENERAL LIMITATIONS ON LAST PAGE OF NOA SUBMITTED FOR
 THE APPROVED USES OF THIS PRODUCT . THIS NOA EXPIRED ON
 07/14/15.
  
 F) CASEMENT WINDOW SIZE AS SHOWN ON PLANS AND WINDOW
 SCHEDULE FOR WINDOW W20. FLORIDA PRODUCT APPROVAL
 FL15190-R1 SUBMITTED DOESN'T COVER THIS WINDOW WIDTH.
 NOTE: EXTERIOR ELEVATION SHOWS WINDOW W20 TO BE DOUBLE
 CASEMENT. IF WINDOW IS DOUBLE CASEMENT, THEN PROVIDE
 PRODUCT APPROVAL FOR CASEMENT WINDOW WITHOUT MULLION IN
 THE MIDDLE. OTHERWISE, REVISE PLANS AS REQUIRED.
  
 11- A)DESIGNER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 B) PLEASE PROVIDE REVIEW STAMP ON COVER SHEET NOT ON
 THE BACK OF THE COVER SHEET.. REVIEW STAMP ON BACK OF
 COVER SHEET DOESN'T ALLOW PROPER SCANNING AND FILING
 FOR THE RECORD RETENTION. SEC. 107.2.1.4 CITY
 AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPIES FOR REFERENCE. PLEASE REMOVE VOID
 SHEETS FROM STAPLED SETS.
  