| 2015-09-10 18:00:22 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS FOR |
| | THE CARRIAGE HOUSE AS REQUIRED BY SEC. R403.6.1 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | NOTE: COORDINATE WITH THE ENERGY CALCULATIONS TO AVOID |
| | CONFLICTS AND DELAYS. |
| | |
| | 2- DRAWING M.01 SUBMITTED NEEDS TO HAVE THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS |
| | REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- THE BEDROOM NEEDS TO COMPLY WITH THE BALANCED RETURN |
| | AIR SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). MECHANICAL PLAN INDICATES A LOUVERED DOOR FOR |
| | THE BEDROOM. LOUVERED DOOR IS NOT SPECIFIED BY THE |
| | ARCHITECT FOR THE BEDROOM. BESIDES, A LOUVERED DOOR FOR |
| | THE BEDROOM IS NOT VERY PRACTICAL AND MAY BE REPLACED. |
| | THEREFORE IS NOT ACCEPTABLE. THE BALANCED RETURN AIR IS |
| | TYPICAL DONE BY INSTALLING TRANSFER GRILLS OR TRANSFER |
| | DUCTS. SEE SEC. M1602.4 AND REVISE AS REQUIRED. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | SUBMIT OLD COPIES FOR REFERENCE. |
| | |